Amendment to chapter 5.1.1.2 "Application: Wiring a load to the digital output, PP switching", 5.1.1.4 "Application:
Wiring of two parallel loads to the digital output, PP switching" and 5.4.2 "Safety-related shutdown of standard output
modules, PP switching" of the manual "Power module F-PM-E 24VDC/8A PPM ST (6ES7136-6PA00-0BC0)"
WARNING
The light test must be activated if the output channel can permanently carry the "0" signal for 100 hours or more. Consult
the respective requirements of your product standards regarding error detection time.
Addendum to section 5.1 "Applications for the output DQ/P1 and P2" and 5.4 "Applications for the safety-related
shutdown of standard modules" of the manual "Power module F-PM-E 24VDC/8A PPM ST (6ES7136-6PA00-0BC0)"
WARNING
A defective F-module can result in cyclic "1" signals with the duration of the "Max. readback time switch on test" at the
output DQ/P1 and P2.
Correction of section 3.1 "Terminal assignment" of the manual "Power Module F-PM-E 24VDC/8A PPM ST (6ES7136-
6PA00-0BC0)"
The warning in the section "Redundant ground conductor required" is being omitted, and being replaced by the new warning
in section 5.1.1.2 "Application: Wiring a load to the digital output, PP switching", section 5.1.1.4 "Application: Wiring two
loads in parallel to the digital output, PP switching" and section 5.4.2 "Safety-related shutdown of standard output modules,
PP switching".
Amendment to chapter 5.1.1.2 "Application: Wiring a load to the digital output, PP switching", section 5.1.1.4
"Application: Wiring two loads in parallel to the digital output, PP switching" and section 5.4.2 "Safety-related
shutdown of standard output modules, PP switching" of the manual "Power module F-PM-E 24VDC/8A PPM ST
(6ES7136-6PA00-0BC0)"
WARNING
In this application, you have to connect two ground cables to the BaseUnit for safety reasons. Otherwise, the maximum
residual current at signal "0" (specified in the technical specifications) cannot be maintained if a single ground cable is
interrupted.
Amendment to chapter 5.2 "Application 1: Safety mode SIL3/Cat.3/PLd" of the Equipment Manual "Digital input module
F-DI 8x24VDC HF (6ES7136-6BA00-0CA0)" and section 5.2.2 "Application 1: Safety mode SIL3/Cat.3/PLd" of the manual
"Power module F-PM-E 24VDC/8A PPM ST (6ES7136-6PA00-0BC0)"
Note
SIL3/Cat.3/PLd can be achieved through cross-circuit proof wiring and for the sensor, through application of the principle of
positive opening operation.
Unsupported parameters
The "Pulse stretching" and "Disable dark test for 48 hours" parameters are not supported.
Dependencies between the "Discrepancy time" and "Input delay" parameters
The configured discrepancy time must be greater than the configured input delay.
Dependencies between the "Startup time of the sensors after short circuit test" and "Time for short circuit test"
parameters
The startup time of the sensor after a short-circuit test must amount to at least 1% of the time for the short-circuit test.
Switching on the supply voltage L+ for the ET 200SP F-modules and IM
Make sure that the F-module as well as the IM were de-energized at the same time before you switch on the supply voltage
L+ for an F-module. You do not have to observe a switch-on sequence.
Cyclic reading of I&M data
Cyclic reading of I&M data can affect the timing of the F-modules. You should therefore avoid short read cycles of less than
500 ms.
16
Product Information for the Documentation of ET 200SP Fail-safe Modules
A5E32586870-AK, 02/2024