Descargar Imprimir esta página

Siemens 6ES7136-6BA00-0CA0 Informacion De Producto página 21

Módulos failsafe

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 43
WARNING
To achieve SIL3/Cat.4/PLe with this wiring, you must use suitably qualified sensors.
WARNING
All cables need to be laid in such a way that they are resistant to interference voltage. Use shielded cables.
Assignable parameters for Application 6
Table 2
Parameters for Application 6 of the F-AI 4xU 0..10V HF
Parameter
Standard value
Discrepancy time
Tolerance window %, absolute
Tolerance window %, relative
Behavior after channel faults
Interference frequency suppression
Evaluation of the sensors
Measuring range
Diagnostics: Wire break
Smoothing
Amendment to section 5.1 "Application 1: Safety mode SIL3/Cat.3/PLd with 2-wire transducer" of the Equipment
Manual "Analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF (6ES7136-6AA00-0CA1)"
WARNING
In the case of 1oo1 evaluation, faults with the sensor or wiring of the F-AI module are not detected.
Amendment to section 5.3 "Application 3: Safety mode SIL3/Cat.3/PLd with 4-wire transducer" of the Equipment
Manual "Analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF (6ES7136-6AA00-0CA1)"
WARNING
In the case of 1oo1 evaluation, faults with the sensor or wiring of the F-AI module are not detected.
New section 5.5 "Application 5: Safety mode SIL3/Cat.3/PLd with 3-wire measuring transducer" in the Equipment
Manual "Analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF (6ES7136-6AA00-0CA1)"
Introduction
The following section describes the wiring scheme and the parameter assignment of the F-AI 4xI 0(4)..20mA 2-/4-wire HF for
Application 5: Safety mode SIL3/Cat.3/PLd, 1oo1 evaluation with 3-wire measuring transducer.
Possible diagnostic messages, the error causes and possible corrective measures are specified in the section "Diagnostic
messages".
Product Information for the Documentation of ET 200SP Fail-safe Modules
A5E32586870-AK, 02/2024
Value range in safety mode
MIN
MAX
100 to 30000 ms
2.0 to 20.0%
2.0 to 20.0%
Passivation of the entire F-module
Passivation of the channel
50 Hz
60 Hz
1oo2 evaluation (max. SIL3/Cat.4/PLe)
0 to 10 V
Disable
Enable
1 / 2 / 4 / 8 / 16 / 32 / 64 conversion cycles