WARNING
To achieve SIL3/Cat.3/PLd with this wiring, you must use a suitably qualified sensor.
WARNING
All cables need to be laid in such a way that they are resistant to interference voltage. Use shielded cables.
WARNING
In the case of 1oo1 evaluation, faults with the sensor or wiring of the F-AI module are not detected.
Assignable parameters for Application 5
Table 3
Parameters for Application 5 of F-AI 4xI 0(4)..20mA 2-/4-wire HF
Parameter
Behavior after channel faults
Interference frequency suppression
Evaluation of the sensors
Measuring range
Diagnostics: Wire break
Smoothing
New section 5.6 "Application 6: Safety mode SIL3/Cat.4/PLe with 3-wire measuring transducer" in the Equipment
Manual "Analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF (6ES7136-6AA00-0CA1)"
Introduction
The following section contains the wiring scheme and the parameter assignment of the F-AI 4xI 0(4)..20mA 2-/4-wire for
Application 6: Safety mode SIL3/Cat.4/PLe, 1oo2 evaluation with 3-wire measuring transducer
Possible diagnostic messages, their error causes and possible corrective measures are specified in the section "Diagnostic
message".
Product Information for the Documentation of ET 200SP Fail-safe Modules
A5E32586870-AK, 02/2024
Value range in safety mode
Passivation of the entire F-module
Passivation of the channel
50 Hz
60 Hz
1oo1 evaluation (max. SIL3/Cat.3/PLd)
0 to 20 mA
4 to 20 mA
(in the measuring range 4 to 20 mA)
Disable
Enable
1 / 2 / 4 / 8 / 16 / 32 / 64 conversion cycles