Descargar Imprimir esta página

Galletti AREO i 12MEC Manual De Instalación, Uso Y Mantenimiento página 23

Aerotermos para climatización con motor ec 11-118 kw

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

» Technical data - Cooling mode
AREO i
Power supply
Air flow rate max cooling
Heating capacity
Water flow
Water pressure drop
Total cooling capacity
Sensible cooling capacity
Water flow
Water pressure drop
Sound power level
Power input
(1)
Water temperature 65°C / 55°C, air temperature 15°C - max speed avaible in cooling mode
(2)
Water temperature 7°C / 12°C, air temperature dry bulb 28°C, wet bulb 19°C (53% relative humidity) - max speed avaible in cooling mode
(3)
Sound power measured according to standards ISO 3741 - max speed available in cooling mode
(4)
Referred to max speed available in cooling mode
33MDF
34MDF
V-ph-Hz
230-1-50
230-1-50
m³/h
2601
2414
(1)
kW
16,3
18,9
(1)
l/h
1426
1653
(1)
kPa
4
7
(2)
kW
5,83
9,65
(2)
kW
4,63
6,66
(2)
l/h
1016
1672
(2)
kPa
3
9
(3)
dB(A)
73
72
(4)
W
86
92
43MDF
43TDC
63MDF
230-1-50
400-3-50
230-1-50
400-3-50
3848
4164
4107
25,0
25,8
38,5
2192
2261
3367
8
9
6
12,2
13,4
19,4
8,32
9,14
12,7
2120
2332
3367
8
9
6
68
70
68
139
177
103
63TDF
63MDC
63TDC
230-1-50
400-3-50
4471
5746
6173
42,0
45,6
49,1
3675
3992
4295
7
8
9
23,9
21,1
25,9
15,7
13,7
17,1
4124
3661
4509
11
9
9
72
71
78
131
219
363
AP66001024
23

Publicidad

loading