Installation Procedures
NB:
When the sizes of the main unit don't match the hole on the ceiling, regulate the slot on the hanging
bracket.
Adjusting the level
Adjust the level with a level meter or according
to the following ways:
Make the adjustment as shown in the figure below.
Choice of Blowing Wind from Blower
The blower can select the maximum static pressure and standard static pressure air volume
through the controller, which is set to the standard static pressure before delivery. When the static
pressure rises with the optional device is used,such as high performance filters. the static pressure
selection is performed as follows:
Remote controller setting mode: remote control selects static pressure. In high wind mode, press
the health button 12 times within 5 seconds, the buzzer will reverberate 4 times, set the maximum
static pressure successfully. Press the health button 12 times within 5 seconds, the buzzer will
sound 2 times, the maximum static pressure function will be canceled, and the default setting
will be restored.
RWV05Wired Controller setting mode: keep pressing the key Set and the key ▲ minus 5 seconds
to enter the advanced setting, press the key Fan to switch to the function category b (temperature
zone display), at this time function category code flashes (clock zone display), press the key ▲ or
▼ to switch the value to 11, then press the key Set, the existing static pressure display is performed
in the time zone, and the specific information flashes. When it is flashing, press the key ▲or ▼
to change it.After the change is completed, press the key Set to confirm.
01 means the default standard static pressure,02 means the maximum static pressure.
Static Pressure Range
Model
DVFA-140N-01M22
4. Drainpipes
(when using the high performance filter)
Standard Static Pressure
100
369
liquid pipe
gas pipe
unit: Pa
Max. Static Pressure
200
drain pipe
8
level meter