Installation Procedures
Refrigerant Filling Amount
Add the refrigerant according to the installation instruction of outdoor unit. The addition of R410A
refrigerant must be performed with a measure gage to ensure the specified amount or compressor
failure can be caused by filling too much or little refrigerant.
Connecting Procedures of Refrigerant Tubing
Proceed the flare tube connecting operation to connect all the refrigerant tubes.
Dual wrenches must be used in the connection of indoor unit tubing.
Mounting torque refers to the right table
wrench
Cutting and Enlarging
Cutting or enlarging pipes should be
proceeded by installation personnel
according to the operating criterion if the
tube is too long or flare opening is broken.
Vacuumizing
Vacuumize from the stop valve of outdoor
units with vacuum pump. Refrigerant sealed
in indoor machine is not allowed to use for
vacuumization.
Open All Valves
Open all the valves of outdoor units. [NB: oil
balancing stop valve must be shut up
completely when connected one main unit.]
Checkup for Air Leakage
Check if there is any leakage at the
connecting part and bonnet with hydrophone
or soapsuds.
Outer Diameter of Tubing (mm) Mounting Torque
6.35
9.52
12.7
15.88
19.05
Connecting
1. Connecting circular terminals:
The connecting method of circular terminal
is shown in the Fig. Take off the screw,
connect it to the terminal tier after heading
it through the ring at the end of the lead and
then tighten it.
2. Connecting straight terminals:
The connection methods for the circular
terminals are shown as follows: loosen the
screw before putting the line terminal into
the terminal tier, tighten the screw and confirm
it has been clamped by pulling the line gently.
3. Pressing connecting line
After connecting line is completed, press the
connecting line with clips which should press
on the protective sleeve of the connecting
line.
correct
pressing
13
11.8~13.7N.m
32.7~39.9N.m
49.0~53.9N.m
78.4~98.0N.m
97.2~118.6N.m
Connecting
circular terminals
terminal tier
wrong
pressing
pressing clip