Description
6.1
Description of Wilo-Connect module Yonos MAXO
The Wilo-Connect module Yonos MAXO extends the pump functions to include:
SBM collective run signal as potential-free NO contact
SSM collective fault signal as potential-free NC contact
Control input "Overriding Off" ("Ext. Off") for potential-free NC contact
Main/standby operation with running time-dependent switchover for twin-head pump operation.
NOTICE
Utilisation of the Wilo-Connect module Yonos MAXO dispenses with external contactors and
other switchgears.
6.2
Operating statuses
Signal lamps and signals
Run signal light (green)
Run signal light (green)
Run signal light (green)
Fault signal light (red)
Fault signal light (red)
Fault signal light (red)
Collective run signal contact
Collective run signal contact
Collective fault signal contact
26
Installation and operating instructions • Wilo-Connect Modul Yonos MAXO • Ed.03/2024-02
Status
Meaning
off
No voltage.
on
Voltage applied.
flashing
Control input "Ext. Off" open.
off
There is no fault.
on
A fault has occurred: Pump not running/pump
faulty.
flashing
Dual-pump function not ensured/faulty.
open
closed
open
No mains voltage.
Control input "Ext. Off" open.
A fault has occurred.
Only double pumps:
SBM master pump: Neither the main
pump nor the standby pump is in opera-
tion.
SBM standby pump: Standby pump is not
in operation.
Pump pumping, there is no fault.
Only double pumps:
SBM master pump: Main or standby
pump is in operation.
SBM standby pump: Standby pump is in
operation.
A fault has occurred: Pump not running/
pump faulty.
Double pumps only:
SSM master pump: One or both parti-
cipants of the double pump is/are faulty.
SSM standby pump: Standby pump is de-
fective.