COMBUSTION ADJUSTMENT
In conformity with EN267 the application of the burner on the boiler, adjustment and testing must be
carried out observing the instruction manual of the boiler, including verification of the CO and CO
concentration in the flue gases, their temperatures and the average temperature of the water in the
boiler.
To suit the required appliance output, fit the nozzle then adjust the pump pressure, the setting of the
combustion head and the air damper opening in accordance with the following schedule.
The values shown in the table are measured on a CEN boiler (as per EN 267).
They refer to 12.5% CO
Nozzle
1
GPH
Angle
2.00
60°
2.25
60°
2.50
60°
3.00
60°
3.50
60°
4.00
60° / 45°
4.50
60° / 45°
1
NOZZLES RECOMMENDED: Monarch type R - PLP ; Delavan type B - W
Angle :
2
PUMP PRESSURE: 12 bar - the pump leaves the factory set at this value
3
COMBUSTION HEAD SETTING : This is done when fitting the nozzle, with the blast tube
Terminal plane of the blast tube
D5284
Blast tube
2404
at sea level and with light oil and room temperature of 20 °C.
2
Pump pressure
2
bar
12
12
12
12
12
12
12
Steinen
60° : in most cases. Particularly suited to avoid flame-detach-
ment during ignition.
45° : for narrow and long combustion-chambers.
14 bar - improves flame retention; it is therefore suitable for ignitions at
low temperatures.
removed. It depends on the output of the burner and is car-
ried out by rotating the regulating rod, till the terminal plane
of the blast tube is level with the set-point, as indicated in
the schedule.
2
5
3
1
Regulating rod
Shutter
Comb. head
Burner output
adjustment
kg/h ± 4%
8.0
9.0
10.0
12.0
14.0
16.1
18.0
type S - SS ; Danfoss type S - B
In the sketch on the left, the combustion
head is set for an output of 3.50 GPH at
12 bar, while the shutter is level with set-
point 3.5, as required by the above
schedule.
4
GB
Air damper
adjustment
3
Set-point
Set-point
1
1.5
2
2.5
3.5
5
6
2
4
2.2
2.6
2.8
3.5
4.0
5.5
6.5