Installation
3. Controls And Indicators
LED indicators
Description of Panel
Controls
ON/OFF
FUNC
Indicators
REC
INV
BYP
BAT
16
Fig 3- 1: Display Panel
1.Press ON/OFF to start inverter when rectifier is OK
NOTE
Not available when UPS is set in automatically start mode
2.Press ON/OFF to shutdown inverter and transfer to bypass
3.Press ON/OFF to shutdown UPS completely when UPS is in
battery mode
4.Press ON/OFF to confirm setting when in setting mode
Functional button:
1.Press FUNC to page down to see LCD menu
2.Press FUNC for 2.5s at the page 1 to mute off, press again to mute
on
3.Press FUNC and ON/OFF together for 2.5s to enter in setting
mode
4.Press FUNC for 2.5s at the page 4 to fault clear
Rectifier indicator: green--rectifier is normal, green flicker--rectifier
is starting, dark—rectifier is not working
Inverter indicator: green--inverter is normal, green flicker--inverter
is starting or tracking with bypass(ECO), dark—inverter is not
working
Bypass indicator: yellow—bypass is normal, yellow flicker—bypass
alarm ,dark—UPS is in normal mode and bypass is normal
Battery indicator: yellow—battery discharged, yellow flicker—No
High Performance 6-10k UPS
LCD
Button
Description
Description