Annex A. Parallel Setting
Annex A. Parallel Setting
1. Connect UPS1 with RS232 cable to PC. Connect UPS with monitoring software.
2. Enter in menu "ServSetting", set System Mode as "Parallel" in the menu "System Setting".
3. Set United Number as "2", set System ID as "0". Press "set" to confirm setting.
4. Connect UPS2 and set System Mode as "Parallel", set United Number as "2", set System ID as 1.
Press "set" to confirm setting.
If there are 3 UPS are paralleled, set the United Number as "3".
5. Connect UPS3 and set System Mode as "Parallel", set United Number as "3", set System ID as 2.