7 Set up with the display and adjustment module
Setup - Max. adjustment -
Interface
Setup - Min. adjustment -
Interface
Setup - Damping
Enter the suitable distance value in m for the empty vessel (e.g.
centage value. The distance refers tot he sensor reference plane (seal
This menu item is only available if you have selected interface meas-
urement under the menu item "Application".
Enter the requested percentage value for the max. adjustment.
Enter the respective distance value in m for the surface of the upper
medium corresponding to the percentage value.
This menu item is only available if you have selected interface meas-
urement under the menu item "Application".
Enter the requested percentage value for the min. adjustment (inter-
face).
Enter the respective distance value in m for the interface correspond-
ing to the percentage value of the interface.
integration time of 0 ... 999 s in this menu item.
If you have selected interface measurement under the menu item
"Application", you can adjust the damping for the level and the inter-
face separately.
-