OPERATION
Antidote:
External-Flush with water.
INTERNAL- Drink large quantities of water or milk.
Follow with milk of magnesia, beaten egg or vegetable oil.
Call physician immediately.
EYES: Flush with water for 15 minutes and get prompt
medical attention. Batteries produce explosive gases. Keep
sparks, flame, cigarettes, etc., away. Ventilate when charging
or using in closed space. Always cover eyes when working
near batteries.
KEEP OUT OF REACH OF CHILDREN
AC parallel operation
Before connection an appliance to either generator, make
sure that it is in good working order and that its electrical
rating does not exceed that of the receptacle.
During parallel operation, the ESC switch should be in
the same position on both generators.
1. Connect the parallel operation cable between
the generator to either an generator or companion
generator following the instructions supplied with
the cable kit.
2. Start the engines and make sure the output indicator
(green) on each generator comes on.
3. Plug an appliance into the AC receptacle.
4. Turn on the appliance.
APPLICATION RANGE
When using the generator, make sure the total load is within rated output of a generator.
Otherwise, generator damage may occur.
AC
Power factor
KN GENI-45
Tip:
• "~" means below.
• Application wattage indicates when each device is used
by itself.
• The simultaneous usage of AC and DC power is possible
but total wattage should not exceed the rated output.
Ex.
Generator rated output
Power factor
Frequency
AC
DC
The overload indicator light comes on when total wattage
exceeds the application range. (See page 4 for more details.).
1
~ 3500 W
~ 2800 W
3500 VA
~ 3500 W
1.0
0.8
~ 2800 W
100 W (12 V / 8.3 A)
--
AC Parallel operation applictions
Tip:
• Make sure thart it is good working order. A faulty
appliance or power cord can create a potential for
electrical shock.
• If an appliance begins to operate abnormally, becomes
sluggish, or stops suddenly, turn if off immediately.
Disconnect the appliance and determine whether
the problem is the appliance, and determine whether
the problem is the appliance or the rated load capacity
of the generator has been exceeded.
• Make sure that the combined electrical rating of
the tools or appliance do not exceed that of
the generator. Never exceed the maximum may be
used for no more than 30 minutes.
• Never connect different generator models.
• Don't remove the parallel operation cable when
the generator operation.
• For single generator operation, the parallel operation
cable must be removed.
WARNING
continuously lights the overload indicator (red) may
damage the generator Marginal overloading that
temporarily light the overload indicator (red) may
shorten the service life of the generator.
• For continuous operation, do not exceed
the rated power.
• Rated power in parallel operation is: 7 kW.
0.8 - 0.95
(efficiency 0.85)
NOTICE
• When supplying precision equipment, electronic
controllers, PCs, electronic computers, microcomputer
based equipment or battery chargers, keep the generator
a sufficient distance away to prevent electrical
interference from the engine. Also ensure that electrical
noise from the engine does not interfere with any other
electrical devices located near the generator.
• If the generator is to supply medical equipment, advice
should first be obtained from the manufacturer, a medical
professional or hospital.
• Some electrical appliances or general-purpose electric
motors have high starting currents, and cannot therefore
be used, even if they lie within the supply ranges given in
the above table. Consult the equipment manufacturer for
8
further advice.
• Substantial overloading that
0.4 - 0.75
~ 1400 W
• Do not overload. The total load of all
electrical appliances must not exceed the
supply range of the generator.
Overloading will damage the generator.
DC
Rated voltage12 v
Rated current 8.3 A