en - Installation notes
Room ventilation
opening for air in-
take from the
setup room
Gas connection
(only for gas-
heated variants)
32
With complex ducting with many bends and additional compon-
ents, or when several different appliances are connected to a
shared duct, it is recommended that a detailed pipework calcula-
tion is carried out by a qualified specialist.
The vent ducting must not be channeled into a chimney or flue
already in use for any gas, coal or oil-burning installation. The warm
and moist exhaust air is to be conducted to the outside or through
suitable ventilation ducting along the shortest path possible. The vent
ducting must be laid so that air flow is not hindered. To achieve this,
use as few bends as possible along with short pipelines and well-
made connections and transitions checked for air-tightness. No filters
or grilles may be fitted in the vent ducting.
The end of the vent ducting leading outside must be protected
against the elements, e.g. with a downward-facing 90° elbow.
 During tumble dryer operation, the room must be adequately
ventilated.
The minimum dimension of the ventilation opening depends on the
cross-section of the extraction ducting.
If the tumble dryer is connected to a central air supply, additional
ventilation openings are normally not needed.
Extraction ducting
150 mm
-
-
150 mm
180 mm
-
-
180 mm
200 mm
-
-
200 mm
220 mm
-
-
220 mm
250 mm
-
-
250 mm
300 mm
-
-
300 mm
The gas connection may only be carried out by a registered install-
ation technician in accordance with the applicable national regula-
tions.
The use of a gas socket for the supply hose is not permitted as
the flow rate is too low for the specified heater rating.
The gas heating is configured at the factory in line with the gas spe-
cifications on the sticker on the rear of the appliance.
Minimum dimension for ventilation opening
A
A
177 cm²
531 cm²
225 cm²
675 cm²
254 cm²
762 cm²
324 cm²
972 cm²
314 cm²
942 cm²
400 cm²
1200 cm²
380 cm²
1140 cm²
484 cm²
1452 cm²
491 cm²
1473 cm²
625 cm²
1875 cm²
707 cm²
2121 cm²
900 cm²
2700 cm²
260 mm
230 mm
295 mm
260 mm
315 mm
280 mm
355 mm
315 mm
350 mm
310 mm
395 mm
350 mm
381 mm
377 mm
430 mm
382 mm
435 mm
385 mm
490 mm
435 mm
520 mm
460 mm
590 mm
520 mm