Default Communication setup Setting options from web page
RS-485
Baud rate
Data bit
Stop bit
Parity
Flow control
Ethernet (SCADA) Default IP address for eDOC
10.1.15.121
Optical Ethernet
Default IP address for eDOC
SCADA
10.1.15.121
Service Ethernet
Default IP address range
10.1.15.x for PC
Default IP address for eDOC
10.1.15.120
Table 5: Summary of communication parameters
For best results it is recommended to configure the Modbus or
DNP3 master with a timeout of 10000 ms and 5 retries.
Minimum delay between polls shall be at least 100 ms.
This product is designed to be connected to and to communicate
information and data via a network interface. It is the user's sole
responsibility to provide and continuously ensure a secure con-
nection between the product and the user network or any other
network (as the case may be). Users shall establish and maintain
any and all appropriate measures (such as, but not limited to, the
installation of firewalls, application of authentication measures,
encryption of data, installation of anti-virus programs, etc.) to
protect the product, the network, its system, and the interface
against any kind of security breaches, unauthorized access, in-
terference, intrusion, leakage and/or theft of data or information.
COMEM SpA is not liable for damages and/or losses related to
such security breaches, any unauthorized access, interference,
intrusion, leakage and/or theft of data or information.
If you are planning on connecting to the Ethernet port or
the optional Ethernet port, contact your network adminis-
trator to confirm the network settings and check that the
service ports described in the table below are accessible.
The SCADA Ethernet port and the optional Ethernet port
are configured with a static IP address. The default server
address on the scada port is 10.1.15.121. Ethernet ports
may also be configured with static IP settings. The SER-
VICE Ethernet port is configured with a static IP address,
so you must set your laptop/PC in the 10.1.15.x range. The
default server address on the service port is 10.1.15.120.
For more information see the "eDOC web interface" man-
ual instruction.
Application
Web interface
IEC61850
MODBUS
DNP3
Table 6: Application TCP ports
9600
Baud rate
8
Data bit
1
Stop bit
None
Parity
None
Flow control
Static IP; DHCP client Administrator settings on
SCADA port can be enabled or disabled using the
web interface. When the fiber optic port is in use,
the Ethernet SCADA port must not be used.
Static IP; DHCP client Administrator settings on
SCADA port can be enabled or disabled using the
web interface. When the fiber optic port is in use,
the Ethernet SCADA port must not be used.
Static IP
NOTE
NOTE
Port
443/tcp
102/tcp
502/tcp
20000/tcp
4800; 9600; 19200; 38400; 57600;
115200
7; 8
1; 2
None; Even; Odd
None
Preparing for installation
This chapter explains the various steps necessary to
physically install the eDOC on the transformer
In accordance with IEC61010-1, to prevent contamination of
the electronics by outside elements the product cover shall be
removed only under controlled environmental conditions defined
as: Temperature shall be 5 °C to 40 °C. Maximum relative
humidity 80% for temperatures up to 31 °C, decreasing linearly
to 50% relative humidity at 40 °C. Do not expose the interior of
the eDOC to rain or snow.
Installation on the transformer valve
The eDOC is designed to be installed on a 1.5 NPT tran-
sformer valve, as explained below:
1.
Loosen the eight rotating flange screws with the
5 mm Allen key.
2.
Wrap the product male fitting thread with PTFE tape.
Protocol
4800; 9600; 19200; 38400;
57600; 115200
Web https port 443/tcp
Modbus TCP port 502/tcp
DNP3 port 20000/tcp
IEC61850 MMS port 102/tcp
Web https port 443/tcp
Modbus TCP port 502/tcp
DNP3 port 20000/tcp
IEC61850 MMS port 102/tcp
Web https port 443/tcp
Modbus TCP port 502/tcp
WARNING