3.
Install the eDOC on the transformer valve. An optional
adapter can be used if the valve fitting is not 1.5 in.
4.
Tighten with a 2 in. (50.8 mm) wrench or use an
adjustable wrench.
5.
Once fully tightened, make sure that the product
is in horizontal position with the sampling access
panel pointing upwards. Rotate the eDOC as
required to achieve this position.
Failure to position the eDOC horizontally, with the access panel
pointing upwards, will cause the thermal pump to malfunction
and may result in erroneous readings.
6.
With the 5 mm Allen key, tighten the rotating flange
nuts to a torque of 8.1 N-m (6.0 lb-ft) according to
the following tightening pattern.
Start running in all the bolts or nuts a few threads
and then run them hand-tight. Tighten by hand, then
according to the torque specification.
Do not over tighten
8
NOTE
NOTE
Bleeding the eDOC
You must bleed the eDOC to make sure that no air is
present in the system:
1.
With the 5 mm Allen key, remove the external
sampling port cover located on top of the product.
2.
Connect the sampling adapter to your bucket (for oil
collection) with a bleeding hose (ID 1/8 in.).
3.
With the 5 mm Allen key, loosen the bleed screw.
4.
Slowly open the transformer valve and wait until oil
comes out of the eDOC.
5.
Tighten the bleed screw to a maximum torque of
2.26 N·m (20 lbf.in).
OIL DIAGNOSTIC DEVICE TYPE EDOC