10.1.2 Sunny Boy Storage 6.0-US
AC connection
Rated power
Maximum apparent AC power
Rated grid voltage
AC voltage range
Nominal AC current
Maximum output current during stand-alone
mode
Total harmonic factor of output current
Maximum residual output current
Duration of the maximum residual output current
Line synchronization characteristics/inrush cur-
rent
Rated grid frequency
Limits of accuracy of voltage measurement
Limits of accuracy of frequency measurement
Limits of accuracy of time measurement at nomi-
nal trip time
Limits of accuracy of current measurement
Limits of accuracy of power (active/reactive)
measurement
Limits of accuracy of power factor measurement
Limits of accuracy of time measurement
Operating range at AC grid frequency 60 Hz
Output power at +60°C (+140°F)
Power factor at rated power
Range of the displacement power factor (ad-
justable)
Feed-in phases
Connection phases
Overvoltage category in accordance with
UL 1741
Installation Manual
10 Technical Data
SBS6.0-US-10
6000 W
6000 VA
240 V
211 V to 264 V
25 A
32 A
<4 %
198 Apeak
33 ms
Method 2/18.5 A
60 Hz
2% of the AC voltage
±0.1 Hz
± 0.1 %
1% of the AC current
5% of the nominal AC power
0.01
0.001 s
59.3 Hz to 60.5 Hz
> 4000 W
1
0.8
to 0.8
overexcited
underexcited
1
2
IV
SBSxx-US-10-IA-xx-14