2.1 Dimensions

Appearance and ergonomics:
WIDE
AUX
STANDARD
Key:
1. drilling template standard models 138.5 x 29 mm.
wide models from 138,5 x 29 mm to 150x31 mm
2.2 Electrical specifi cations
Power supply
Insulation guaranteed by the power supply insulation from very low voltage parts
Inputs
Type of probe
Relay outputs
Connections

2. POWERCOMPACT SMALL

183.4
167
voltage
model S:
115 - 230 V~ 50/60 Hz;
insulation from relay outputs
S1
NTC or PTC, depending on the model
S2
NTC or PTC, depending on the model
DI1
voltage-free contact, contact resistance < 10 ohm, closing current 6 mA
S3
NTC or PTC, depending on the model
DI2
voltage-free contact, contact resistance < 10 ohm, closing current 6 mA
S4
NTC or PTC, depending on the model
Maximum distance between probes and digital inputs less than 10 m. Note: in the installation, keep the power supply and load connections
separate from the probe, digital inputs, repeater display and supervisor cables.
Std. Carel NTC
High temperature NTC
Std. Carel PTC (specifi c model)
depending on the model
5 A
EN60730-1:
250 V~ 5 (1) A;
UL 873:
250 V~ 5A res 1FLA 6LRA C300;
8 A
EN60730-1:
250 V~ 8 (4) on N.O., 6 (4) on N.C., 2 (2) on N.O. and N.C.; 100,000 operating cycles
UL 873:
250 V~ 8A res 2FLA 12LRA C300;
30 A
EN60730-1:
250 V~ 12 (10) A;
UL 873:
250 V~ 12A res 2HP 72LRA;
Relay not suitable for fl uorescent loads (neon lights, ...) that use starters (ballasts) with phase-shift capacitors. Fluorescent lamps with electro-
nic control devices or without phase-shift capacitors can be used, within the operating limits specifi ed for each type of relay.
insulation from very low voltage parts
insulation between the relay outputs
Type of connection
fi xed screw
plug-in for screw blocks
fi xed screw vertical
spade with crimped contact
The correct sizing of the power and connection cables between the instrument and the loads is the responsibility of the installer.
Maximum current at terminals 4 and 7 is 12A. In the max load and max operating temp. conditions, the cables used must be suitable for ope-
ration up to 105°C.
10
da 138.5 a 150 x 31mm
Fig. 2.a
power
6 VA, 50 mA~ max
reinforced; 6 mm air, 8 mm surface; 3750 V insulation
basic; 3 mm air, 4 mm surface; 1250 V insulation
10 k at 25 °C, range –50 to 90 °C
measurement error: 1 °C in the range –50 to 50 °C
3 °C in the range +50 to 90 °C
50 k at 25 °C, range –40 to 150 °C
measurement error: 1.5 °C in the range –20 to 115 °C
4 °C in the range outside of -20 to 115 °C
985  at 25°C, range -50 to 150 °C
measurement error: 2 °C in the range –50 to 50 °C
4 °C in the range +50 to 150 °C
reinforced; 6 mm air, 8 mm surface; 3750 V insulation
basic; 3 mm air, 4 mm surface; 1250 V insulation
Cross-sections
for cables from 0.5 to 2.5 mm
ir33 platform "connections" +030220447 - rel. 2.2 - 15.06.2010
40
45
8
dima di foratura
drilling template
153.5
165
100,000 operating cycles
30,000 operating cycles
30,000 operating cycles
100,000 operating cycles
30,000 operating cycles
Maximum current
2
12A