3.1 Dimensions
3.2 Technical specifi cations
Power supply
Insulation guaranteed by the power supply
Inputs
Type of probe
Relay outputs
Connections
ir33 platform "connections" +030220447 - rel. 2.2 - 15.06.2010
3. MASTERCELLA 2
voltage
model E:
230 V~ 50/60 Hz;
model A:
115 V~ 50/60 Hz;
voltage
model E, A:
insulation from very low voltage parts
insulation from relay outputs
S1
NTC or PTC, depending on the model
S2
NTC or PTC, depending on the model
DI1
voltage-free contact, contact resistance < 10 ohm, closing current 6 mA
S3
NTC or PTC, depending on the model
DI2
voltage-free contact, contact resistance < 10 ohm, closing current 6 mA
S4
NTC or PTC, depending on the model
DI3
voltage-free contact, contact resistance < 10 ohm, closing current 6 mA
S5
NTC or PTC, depending on the model
Maximum distance between probes and digital inputs less than 10 m. Note: in the installation, keep the power supply and load connec-
tions separate from the probe, digital inputs, repeater display and supervisor cables.
Std. Carel NTC
High temperature NTC
Std. Carel PTC (specifi c model)
measurement error: 2 °C in the range -50 to 50 °C
depending on the model
8 A (*)
EN60730-1:
250 V~ 8 (4) on N.O., 6 (4) on N.C., 2 (2) on N.O. and N.C.; 100,000 operating cycles
UL 873:
250 V~ 8A res 2FLA 12LRA C300;
16 A (*)
EN60730-1:
250 V~ 10 (4) A up to 60°C on N.O., 12 (2) A on N.O. and N.C.;100,000 operating cycles
UL 873:
250 V~ 12A res 5FLA 30LRA C300;
2HP
EN60730-1:
250 V~ 10 (10) A;
UL 873:
250 V~ 12A res 12FLA 72LRA;
30 A (*)
EN60730-1:
250 V~ 12 (10) A;
UL 873:
250 V~ 12A res 2HP 72LRA;
(*): relay not suitable for fl uorescent loads (neon lights, ...) that use starters (ballasts) with phase-shift capacitors. Fluorescent lamps with
electronic control devices or without phase-shift capacitors can be used, within the operating limits specifi ed for each type of relay.
insulation from very low voltage parts
insulation between the relay outputs
Type of connection
fi xed screw
plug-in for screw blocks
spade with crimped contact
wire cross-section for probes and digital inputs:
wire cross-section per power supply and loads:
The correct sizing of the power and connection cables between the instrument and the loads is the responsibility of the installer.
In the max load and max operating temp. conditions, the cables used must be suitable for operation up to 105°C.
Fig. 3.a
power
11,3 VA, 50 mA~ max
11,3 VA, 100 mA~ max
power
reinforced; 6 mm air, 8 mm surface; 3750 V insulation
basic; 3 mm air, 4 mm surface; 1250 V insulation
10 k at 25 °C, range -50 to 90 °C
measurement error: 1 °C in the range -50 to 50 °C
3 °C in the range +50 to 90 °C
50 k at 25 °C, range -40 to 150 °C
measurement error: 1.5 °C in the range -20 to 115 °C
4 °C in the range outside of -20 to 115 °C
985 at 25°C, range -50 to 150 °C
4 °C in the range +50 to 150 °C
reinforced; 6 mm air, 8 mm surface; 3750 V insulation
basic; 3 mm air, 4 mm surface; 1250 V insulation
Cross-sections
for cables from 0.5 to 2.5 mm
2
13
30,000 operating cycles
30,000 operating cycles
100,000 operating cycles
30,000 operating cycles
100,000 operating cycles
30,000 operating cycles
Maximum current
12A
0.25 to 2.5 mm2 (from 20 to 13 AWG)
1.5 to 2.5 mm2 (from 15 to 13 AWG)