KCER-01MF
Multifunction Tester
5.2.5.1 Using the Functions activated by F1 button
5.2.5.2 Using the AUTO Mode
1. Turn the rotary switch to the RCD position
2. Initial screen is setup to the AUTO
3. Using the F2 and F3 button, select the rating and the type of the RCD
4. Connect test leads as shown in the Figure 5.2.4.1
5. If --- from the lower right corner disappears and voltage of the L- PE on the lower left appears, the
unit is ready to TEST
(If N and PE test leads are reversed, the instrument will still carry out the test)
6. Press the TEST button when ready
7. Test will proceed it should not trip from x 1/2 mode but will trip from the x 1 0° mode, and indicate the
trip time
8. Reset RCD the unit will measure the Trip Time from the x 1 180° mode
9. Repeat for both x 5 0° and x 5 180° resetting RCD after each test
10. Tests now complete - see display for results
5.2.4.3 Using the x1/2, x1, x2 and x5 manual selection
1. Turn the rotary switch to the RCD position
2. Press F1 and aspect button from the AUTO to select x1/2, x1,x2, and x5
3. Using the F2 and F3 button, select the RCD's trip current and type of the RCD. (General/Selective)
28
Figure 15 RCD Measurement – Test lead connection
Figure 16 RCD Auto Function Screen