2. SPECIFICATION

LOOP Resistance
L- PE (Hi-Amp)
Range (Ω)
0.23 – 9.99
10.0 – 99.9
100 – 999
Measuring Current ......................................................................... 8.0 A-25.0A
Range of the Voltage Used ...............................................................195V a.c. – 260V a.c. (50,60Hz)
Notes
[1] Valid for resistance of neutral circuit <20Ω and up to a system phase angle of 30°.Test leads must be
zeroed before testing.
[2] Valid for mains voltage >200V.
L- PE (No Trip)
Range (Ω)
0.23 – 9.99
10.0 – 99.9
100 – 999
Measuring Current .......................................................................... < 15mA
Range of the Voltage Used ...............................................................195V a.c – 260V a.c (50,60Hz)
Notes
[1] Valid for resistance of neutral circuit <20Ω and up to a system phase angle of 30°.Test leads must be
zeroed before testing.
[2] Valid for mains voltage >200V.
LINE Resistance
L- N
Range (Ω)
0.23 – 9.99
10.0 – 99.9
100 – 999
Measuring Current ......................................................................... 4.0 A
Range of the Voltage Used ...............................................................195V a.c. – 260V a.c. (50,60Hz)
Notes
[1] Valid for resistance of neutral circuit <20Ω and up to a system phase angle of 30°.Test leads must be
zeroed before testing.
[2] Valid for mains voltage >200V.
RCD (EN 61557-6)
Rcd Rating (I_n) .........................................10mA, 30mA, 100mA, 300mA, 500mA and 1A.
Test current ............................................. x1/2, x1, x2 and x5
Accuracy at applied test current
Current Multiplier
x1/2
x1
x2
X5
5
Resolution(Ω)
0.01
0.1
1
Resolution(Ω)
0.01
0.1
1
Resolution(Ω)
0.01
0.1
1
Trip Time Accuracy
±(1% of reading+ 1 digits)
±(1% of reading+ 1 digits)
±(1% of reading+ 1 digits)
±(1% of reading+ 1 digits)
Accuracy
±(4% of reading+ 6
digits)
Accuracy
±(5% of reading+ 6
digits)
Accuracy
±(4% of reading+ 4
digits)