(A)
mm
A
B
RL 190/M
1200
850
(B)
mm
A
B
RL 190/M
813
366
(C)
C
kg
800
C
D
E
F
G
447
555
712
370
222
D3931
D36
D1217
H
I
430
1166
3
BURNER DESCRIPTION (A)
1 Ignition electrodes
2 Combustion head
3 Screw for combustion head adjustment
4 Screw for fixing fan to flange
5 Oil pressure switch
6 Pressure gauge for pressure on nozzle
return
7 Pressure gauge for pressure on nozzle deliv-
ery
8 Pump
9 Nozzle holder
10 Air gate valves
11 Safety solenoid valve
12 Fan pressure test point
13 Boiler mounting flange
14 Flame stability disk
15 Slide bars for opening the burner and
inspecting the combustion head
16 Extensions for slide bars 15)
17 Electrical motor
18 Ignition transformer
19 Motor contactor and thermal cut-out with
reset button
20 Power switch for different operations:
automatic - manual - off.
Button for:
power increase - power reduction
21 Terminal strip
22 Fairleads
for
electrical
installer
23 Control box with lock-out pilot light and lock-
out reset button
24 Flame inspection window
25 Photocell for flame presence control
26 Valve assembly with pressure regulator on
nozzle return
27 Servomotor, provides adjustment of fuel
delivery regulator and of air gate valve.
When the burner is not operating the air gate
valve is fully closed in order to reduce to a
minimum heat dispersion from the boiler due
to the flue draught which draws air from the
fan suction inlet.
Two types of burner failure may occur:
Control Box Lock-out: if the control box 23)(A)
pushbutton lights up, it indicates that the burner
is in lock-out.
To reset, press the pushbutton, no sooner than
10 s after the lock-out.
Motor trip: release by pressing the pushbutton
on thermal relay 19)(A).
PACKAGING - WEIGHT (B)
Approximate measurements
The burners stands on a wooden base which
can be lifted by fork-lifts. Outer dimensions of
packaging are indicated in (B).
The weight of the burner complete with pack-
aging is indicated in Table (B).
- 
MAX. DIMENSIONS (C)
Approximate measurements
The maximum dimensions of the burner are
given in (C).
Bear in mind that inspection of the combustion
head requires the burner to be opened and the
rear part withdrawn on the slide bars.
The maximum dimension of the burnerwhen
open, without casing, is give in measurement I.

STANDARD EQUIPMENT

2 - Flexible hoses (L = 1340 mm)
2 - Gaskets for flexible hoses
2 - Nipples for flexible hoses
1 - Thermal insulation screen
4 - Extensions 16)(A) for slide bars 15)(A)
4 - Screws to secure the burner flange to the
boiler: M 16 x 40
1 - Instruction booklet