General
Th ere are two levels of protection for parameters:
a) Direct (D): with immediate access, User-changeable;
b) Password protected (U): password required for access; Factory-set
parameters.
4.4.1
Sensor parameters
PARAMETER
CODE
/23
Unit of measurement
4.4.2
Regulator parameters
PARAMETER
CODE
r01
Summer set point.
r02
Summer diff erential.
4.4.3
Anti-frost/B2 backup heating element parameters
PARAMETER
CODE
A01
B2 anti-frost alarm set point.
A02
Anti-frost alarm diff erential.
B2 cooling anti-frost heating
A04
element set point.
B2 cooling backup heating ele-
A05
ment diff erential.
Automatic anti-frost switch-on
A10
(section 4.4.3.1).
4.4.3.1
Automatic anti-frost switch-on
0
Disabled.
1
Heating element and pump on simultaneously at
2
Heating element and pump on independently at
3
Heating element and pump on at
A04
4.4.4
Visualization sensor parameters B1/B2
PARAMETER
CODE
Visualization sensor B1
b01
(water out)
Visualization sensor B2
b02
(evaporator)
4.4.5
Alarm parameters
PARAMETER
Level alarm delay aft er pump start.
Normal operating level alarm
delay.
Low pressure alarm delay aft er
TYPE
DEFAULT
compressor switch-on.
0
U
B1 high temperature alarm set
point.
TYPE
DEFAULT
B1 low temperature alarm set
12.0
point.
D
3.0
4.4.6
Compressor parameters
D
PARAMETER
Minimum `On' time.
TYPE
DEFAULT
3.0
Minimum `Off ' time.
D
5.0
Time between two compressor
D
switch-ons.
5.0
D
Switch-on delay.
Compressor switch-on delay aft er
1.0
D
pump start.
Pump switch-off delay.
0
U
Compressor hour counter.
Functioning hour counter
threshold.
Pump hour counter.
A04
.
Minimum time between two
A04
.
pump switch-ons.
.
Minimum pump on time.
4.4.7
General parameters
TYPE
DEFAULT
PARAMETER
D
Enable digital input on/off .
Enable keypad.
D
Serial address.
4.5
Parameter management
4.5.1
Temperature setting (see fi g.1)
1. Turn the main swicth (QS) to "ON" and wait for the temperature
visualization.
2. Press and hold button "P2" (SEL) for more than 5 seconds to access
ICE007-010
CODE
TYPE DEFAULT
P01
5
U
P02
5
U
P03
120
U
P16
80.0
U
P19
-40.0
U
CODE
TYPE
DEFAULT
c01
0
U
c02
0
U
c03
360
U
c06
0
U
c07
5
U
c08
0
U
c10
0
D
c14
0
U
c15
0
D
c17
0
U
c18
0
U
CODE
TYPE
DEFAULT
H07
1
U
H09
1
U
H10
1
U
the menu "D".
3. Select the parameter "-r-" using the "P3" and "P4" buttons, then
press button "P2" (SEL) to enter.
4. Select the parameter "r01" using the "P3" and "P4" buttons, then
press button "P2" (SEL) to enter.
5. Change the value, using the up and down arrow buttons "P3" and
"P4", then press button "P2" (SEL) to exit and save.
6. Press button "P1" (PRG) to exit.
4.5.2
Diff erential setting (see fi g.1)
1. Turn the main swicth (QS) to "ON" and wait for the temperature
visualization.
2. Press and hold button "P2" (SEL) for more than 5 seconds to access
the menu "D".
3. Select the parameter "-r-" using the "P3" and "P4" buttons, then
press button "P2" (SEL) to enter.
4. Select the parameter "r02" using the "P3" and "P4" buttons, then
press button "P2" (SEL) to enter.
5. Change the value, using the up and down arrow buttons "P3" and
"P4", then press button "P2" (SEL) to exit and save.
6. Press button "P1" (PRG) to exit.
4.5.3
Visualization sensor B1,B2
1. Press and hold button "P2" (SEL) for more than 5 seconds to access
the menu "D".
2. Select the parameter "-b-" using the "P3" and "P4" buttons, then
press button "P2" (SEL) to enter.
3. Select the parameter "b01" or "b02" using the "P3" and "P4"
buttons, then press button "P2" (SEL) to see the temperature.
4. Press button "P1" (PRG) to exit.
4.6

Alarms management

4.6.1
Digital input alarms
ID
CODE
DESCRIPTION
tP
ID1
Pump thermal cutout alarm. / Phases
monitor
FL
ID2
Water tank low water level alarm / No
water fl ow.
HP1
ID3
High pressure alarm from pressure
switch.
LP1
ID4
Low pressure alarm from pressure
switch.
4/6
RESET
M
A
M
M