Concrete Slab - Briggs & Stratton 35000 Serie Manual De Instrucciones

Tabla de contenido

Publicidad

Concrete Slab

At the appropriate location, construct a concrete slab:
• 28 day compression strength of 3000 psi (200 MPa)
• Minimum 5" (13cm) thick
• Minimum 6" (15cm) wider than enclosure on all sides
(shown as D in figure)*
• Strengthen slab with No. 6 reinforcing bars (on 12"
(30.5cm) centers) or 8 ga. steel wire fabric
(6" (15cm) centers).
Avoid placing reinforcement in entrance stub-up area (shown as B).
Attach unit to slab at four corner locations (A) with minimum
5/16" diameter (8mm) (per local requirements) masonry
anchor bolts long enough to secure the unit.
The fuel inlet location (C),the concrete slab, and the exhaust
outlet (E) are shown for reference.
• The standby generator enclosure (F)measures
86" (203 cm) X 37" (94 cm).
14
7-1/2"
19cm
7-1/4"
18.4cm
9"
22.9cm
42"
106.7cm
78"
198.1cm
A Holes located in base to anchor to pad
B Stub up Area
C Fuel Inlet
D Concrete slab
E Exhaust Outlet
F Standby Generator Enclosure
34-1/4"
87cm
5"
12.7cm
A
B
C
F
D
E
BRIGGSandSTRATTON.COM

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

76160

Tabla de contenido