 while carefully turning insert tube element (8) with scale 41 - 75 hPa (41 - 75 mbar) into
fixed tube element (7).
 while carefully turning insert tube element (9) with scale 81-115 hPa (81-115 mbar) into
tube element (8).
 while carefully turning insert tube element (10) with scale 121-115 hPa (121-115 mbar) in-
to tube element (9)
 Open connecting valves B, C and D
 Use bellow (12) to load a pressure pursuant to 1* into the test system.
 Close connecting valve C to avoid a loss in pressure.
 Wait 10-60 minutes (dependent on pipe volume) for loaded air and water temperatures to
equalize.
Prolong 10-60 minute period of temperature equalization if temperatures fluctuate
greatly. The equalization period can last up to two hours!
 Carry out the test over a period prescribed by 1*. Over this period the pressure indicated
must not drop.
Leak testing: Adjustment times and test duration depending on the line volume
line volume*
< 100 l
≥ 100 l < 200l
≥ 200l
 * benchmarks
5.3
Adjustment of gas admission pressure to atmosperic and blower burners using
water column up to 30 hPa (30 mbar)
Complete test as described 5.2:
The fixed tube element (7) up to 30 hPa (30 mbar) is sufficient for this test type.
 Connect gas appliance adapter (21) to the open end of the connecting hose (6).
 Connect the snout of the gas appliance adapter (21) to the test supply system of the gas
appliance.
 Set the gas appliance burner to the highest possible setting.
 Open connecting valves B and D.
 Read the actual gas admission pressure.
5.4

Initial test of drinking water systems of domestic connections

Complete test as follows:
 Close all cut-off valves on your ROTEST GW 150/4.
 Insert connecting hose (6) to connecting valve A. An auditable sound is heard when hose
and valve nipple are properly locked.
 Insert open end of the connecting hose (6) to your adapter of the end of pipe. An auditable
sound is heard when hose and adapter nipple are properly locked.
 Use hand pump (3) to load a pressure pursuant to 1* into the test system
 Wait 10 minutes for loaded air and water temperatures to equalize.
Prolong 10-60 minute period of temperature equalization if temperatures fluctuate
greatly. The equalization period can last up to two hours!
 Carry out the test over a period prescribed by 1*. Over this period the pressure indicated
must not drop.
Adjustment time
10 min.
30 min.
60 min.
ENGLISH
At least test duration
10 min.
20 min.
30 min.
13