_CombiPower_IA_DE-IT.book Seite 96 Freitag, 21. Oktober 2011 8:10 20
Configuring the device with the remote control
"O/P Parameter" menu (output parameters)
Parameter
Explanation
O/P Voltage Output voltage
O/P
Output voltage frequency
Frequency
Sync
Output voltage frequency toler-
Frequency
ance for synchronisation
If the frequency tolerance is
disabled, the output voltage
frequency ranges between 47
and 63 Hz.
Overload
Percentage power at which an
Alarm
overload alarm is triggered
Saving
Specifies the energy saving
Level
mode: minimum load for switch-
ing on again
Disable = never
1 = 40 VA
2 = 80 VA
3 = 100 VA
4 = 120 VA
5 = 160 VA
6 = 180 VA
7 = 220 VA
Saving
Interval at which the system
Interval
checks whether a consumer unit
with the minimum load is
switched on
96
Value range
200 Vw – 240 Vw
47 Hz – 63 Hz
Disabled,
0.1 Hz – 7 Hz
50% – 110%
Disabled, 1 – 7
0.1 – 2 sec.
CombiPower
Default
230 Vw
50 Hz
7 Hz
100%
Disabled
2 sec.
EN