INSTALLATION
11.5
Electrical characteristics
Fig. 11.3
Electrical layout for outdoor and indoor connection.
Legend
1
Connector strip for the outdoor unit
2
Connector strip for the indoor unit
A + B
VAM 6-050 W2N / VAM 6-060 W2N
A + B + C
VAM 6-085 W3N
A + B + C + D
VAM 6-085 W4N
Power supply (V/Ph/Hz)
Supply section up to 25 meter (in mm
Indoor / Outdoor
Thermal-magnetic circuit breaker, type D (A)
Interconnection section up to 25 meter (mm
Inteconnect shielded cable or not (YES / NO)
Immediatte residual current protector (A)
Table 11.1 Electrical Characteristics.
18
VAM 6-050 W2N
220-240V / 1 / 50
)
2.5
2
Outdoor unit
20
)
2.5
2
NO
0.03
VAM 6-060 W2N
VAM 6-085 W3N
220-240V / 1 / 50
220-240V / 1 / 50
2.5
4
Outdoor unit
Outdoor unit
20
25
2.5
2.5
NO
NO
0.03
0.03
VAM 6 MWN-I_EN - 09/14 - Vaillant
VAM 6-085 W4N
220-240V / 1 / 50
4
Outdoor unit
25
2.5
NO
0.03