User Manual Wired Controller
units. Please refer to 3.2.3 Parameters Setting.
(2) When two wired controllers control one indoor unit, the addresses of those two
wired controllers should be different. Please refer to 3.2.3 parameter setting.
(3) When two wired controllers control multiple indoor units, wired controller can
connected to any one indoor unit, while the connected indoor unit should be the
same series indoor unit. The addresses of those two wired controllers should be
different. Please refer to 3.2.3 parameter setting. The total quantity of indoor unit
controlled by wired controller can't be more than 16 sets and all connected indoor
units must be within the same indoor unit network. Wire controller must set quantity
of group control indoor units. Please refer to 3.2.3 Parameters Setting.
(4) When one (or two) wired controller(s) control(s) multiple indoor units at the same
time, the controlled indoor unit's setting should be the same.
(5) Wiring of wired controller and indoor unit network must be according to one of the
four wiring method as shown in fig 3.3-3.6. As for the connection method shown in
fig 3.4 and 3.6, there should be only one master wired controller (address is 01) and
one slave wired controller (address 02). The quantity of wired controller can't
exceed two.
9