Param
eter
Parameter name
code
P10
Set master indoor unit
Set infrared receiver
P11
of wired controller
Set address of wired
P13
controller
Set quantity of group
P14
control indoor units
Set unit of
P16
temperature
Set static pressure of
P30
indoor fan motor
High ceiling
P31
installation*
Table 3.2 Parameter setting list
Parameter
Defaul
range
t value
00: do not change
current
master/slave state
of indoor unit
01: set current
indoor
unit as master
indoor unit
00: forbidden
01: activated
01: master wired
controller
02: slave wired
controller
00: forbid this
function
01-16: indoor unit
quantity
00:Celsius
01:Fahrenheit
01-09: static
pressure level of
indoor fan motor
00: installation
height of standard
ceiling
01: installation
height of high
ceiling
16
User Manual Wired Controller
When set the corresponding indoor unit of
wired controller as master indoor
00
unit,"MASTER" icon will be bright after
finishing setting.
It can be set only through master wired
controller.
When infrared receiver of wired controller
01
is forbidden, the wired controller can't
receive the signal from remote controller
and it is operated through buttons.
When two wired controllers control one
indoor unit (or several indoor units), the
addresses of the two wired controllers
01
should be different. Assistant wired
controller (02) is without unit parameter
setting function except setting its address.
Set the corresponding value
01
according to the connected indoor unit
quantity.
00
There are two kinds of static pressure
level:
5 levels: 03, 04, 05, 06, 07
9 levels: 01, 02, 03, 04, 05, 06, 07, 08, 09
Wired controller can be adapted to the
different types of indoor units that it
05
possesses 1-9 level selection for setting
static pressure. When the indoor unit with
5 static pressure levels received the level
setting sent by wired controller is less than
3, it will be settled as the 3rd level; if it is
over 7, it will be settled as the 7th level.
00
Only applicable to cassette units
Note
--