Web Server; E-Mail Notification; Glossary - System Sensor 8100E FAAST Instrucciones De Instalación Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 41

WEB SERVER

The FAAST system contains an integrated Web server which is used to observe
detector configuration and may be used to remotely monitor the unit.
The Web server features include:
• Intuitive interface for remote monitoring of faults, relays, particulate level, air
flow, and power supply
• Facility location and contact information
• Configuration settings display
• Multi-Lingual support
• Event log viewer

E-MAIL NOTIFICATION

The FAAST system has the ability to send e-mail notifications to an individual or
organization. Up to 6 different email addresses may be stored for notification. Each
email address can be configured to be notified of a specific alarm level, fault level
or isolate condition through the PipeIQ software. E-mails from the device indicate a
device's ID, location and alarm or fault type.
FIGURE 14. BOTTOM VIEW OF UNIT
Wiring
Access
Plugs

GLOSSARY

KEY TERMS
Configure:
To set up a program or computer system for a particular application.
FAAST Fire Alarm Aspirating Sensing Technology®:
High sensitivity aspirating smoke detection system.
IP Address:
An Internet Protocol (IP) address is a numerical label that is assigned to devices
participating in a computer network utilizing the Internet Protocol for communica-
tion between its nodes.
PipeIQ®:
A software program designed to work with the FAAST unit for system configura-
tion, monitoring and pipe design.
Web server:
A Web server is a computer program that delivers (serves) content. The device
contains an integrated Web server which is used to observe detector configuration
and may be used to remotely monitor the system.
SS-400-015
MAINTENANCE
The only periodic maintenance required is to replace the filter assembly when
the filter light is illuminated. Perform the following procedure to replace the filter
assembly.
1.
2.
3.
4.
5.
6.
7.
8.
Other system checks may need to be performed in accordance with local or na-
tional codes and regulations.
Sampled
Network
Air Inlet
Connection
9
Remove power from the system.
Open the door on the right side of the device that covers the LED system
indicators.
Remove the plastic name card over the LEDs.
Remove the two screws holding the filter assembly into the device.
Remove the filter assembly and replace it with a new assembly.
Lightly tighten the two screws ¼ revolution beyond the first indication of the
torque increase. (0.7nm (newton metres))
Replace the plastic name card over the LEDs.
Close the door and return power to the system.
Sampled
Air Outlet
ASP-03