Gas Supply Line
Provide a gas supply line of 3/4" (1.9 cm) rigid pipe to
the range location. A smaller size pipe on longer runs may
result in insufficient gas supply. With Propane gas, piping or
tubing size can be 1/2" (1.3 cm) minimum. Usually, Propane
gas suppliers determine the size and materials used in
the system.
NOTE: Pipe-joint compounds that resist the action of
Propane gas must be used. Do not use TEFLON
Flexible Metal Appliance Connector:
If local codes permit, a new CSA design-certified,
4 ft to 5 ft (122 cm to 152.4 cm) long, 1/2" or 3/4"
(1.3 cm or 1.9 cm) I.D. (inside diameter), flexible metal
appliance connector may be used for connecting
range to the gas supply line.
A 1/2" (1.3 cm) male pipe thread is needed for
connection to the female pipe threads of the
inlet to the appliance pressure regulator.
Do not kink or damage the flexible metal tubing
when moving the range.
Must include a shut-off valve:
Install a manual gas line shut-off valve in an easily
accessible location. Do not block access to shut-off valve.
The valve is for turning on or shutting off gas to the
cooktop.
A
A. Gas supply line
B. Shut-off valve open position
C. To range
®
TEFLON is a registered trademark of Chemours.
tape.
®†
B
C
Gas Pressure Regulator
The gas pressure regulator supplied with this range must be
used. The inlet pressure to the regulator should be as follows
for proper operation:
Natural Gas:
Minimum pressure: 15 cm WCP
Maximum pressure: 35.6 cm WCP
Propane gas:
Minimum pressure: 27.9 cm WCP
Maximum pressure: 35.6 cm WCP
Contact local gas supplier if you are not sure about the inlet
pressure.
Burner Input Requirements
Input ratings shown on the model/serial/rating plate are for
elevations up to 2,000 ft (609.6 m).
For elevations above 2,000 ft (609.6 m), ratings are reduced
at a rate of 4% for each 1,000 ft (304.8 m) above sea level
(not applicable for Canada).
Gas Supply Pressure Testing
Gas supply pressure for testing regulator must be at least 1"
water column pressure above the manifold pressure shown on
the model/serial/rating plate.
Line Pressure Testing Above 1/2 psi (3.5 kPa) Gauge
(35.6 cm WCP)
The range and its individual shut-off valve must be
disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of
1/2 psi (3.5 kPa).
Line Pressure Testing at 1/2 psi (3.5 kPa) Gauge (35.6 cm
WCP) or Lower
The range must be isolated from the gas supply piping
system by closing its individual manual shut-off valve during
any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psi (3.5 kPa).
11