Caution
Electrical Shock Hazard. Can cause
electrical shock or equipment damage.
Disconnect power supply before connecting wiring.
Wiring must comply with applicable
codes, ordinances and regulations:
1. Wire the C7089 Outdoor Sensor to the
S terminals on the humidity control. If
leadwire provided with C7089 is not
long enough (60 in.), run a cable to a
hole at C7089 location.
• Using color-coded, 18-gauge,
shielded thermostat wire is
recommended. For example of
general wiring of C7089, see image
at right.
• Pigtail wiring can be used.
2. Mount C7089 in its mounting clip.
3. Plug wiring hole using nonhardening
caulk or putty.
1
C7089
1
USE APPROPRIATE MOUNTING MEANS FOR THE
TYPE OF STRUCTURE.
2
PLUG WIRING HOLE WITH NON-HARDENING
CAULK OR PUTTY.
19
WIRING HOLE
THROUGH
STRUCTURE
C
R
U
U
S
S
2
M34611