BREAKDOWN DIAGNOSTIC

User can use the unit after trial operation. Before contacting us, you can make self trouble shooting following below chart in case of
any failure
SYMPTOMS
Fans doesn't work
Motor out of the absorption:
Excessive air flow:
Insufficient air flow:
Noise:
Strong vibrations:

DISMANTLING

The following symbol indicates that this product must not be disposed of as domestic waste. Respect the sorted waste system
based on local laws and regulations.
Contact the local authorities for information about disposal, or request free collection by the manufacturer.
The separate collection of the product, and its recycling at the time of disposal, will help preserve natural resources and protect hu-
man health and the environment.
The materials that make up the unit are:
galvanised sheet metal
EPS (foam polystyrene)
polyethylene
ABS (acrylonitrile butadiene styrene) plastic
NBR (nitrile butadiene rubber)
51
Missing power supply
the switches of the thermostat are not in the right position of working
there are foreign bodies that block the rotors.
Check electrical connections
Pression is low than what is required and then the air flow is excessive. It must increase pressure
drops with calibration dampers.
Excessive density of the fluid. Rotation speed too high.
Pression is low than what is required and then the air flow is excessive. It must increase pressure
drops with calibration dampers.
Excessive density of the fluid. Rotation speed too high.
Pressure drop of the system are underestimated.
Cloggings in the air ducts.
Rotation speed too low: verify on the terminal board of the motor that the connection is correct and that
the voltage correspond to that of the nameplate.
the rotor turn backwards.
Excessive air flow.
Air leakage from the duct joints.
Unbalanced fan.
Foreign bodies in the case.
Unbalanced impeller because of wear or of dust deposit.
Sliding of the impeller on the case due to deformations.
Cloggings in the air ducts.
POSSIBLE CAUSES