Performance Data
Units with Horizontal Discharg
CAUDAL
Air
50
(l/s)
RPM
BkW
1770
621
0,77
1880
655
0,92
2000
689
1,08
2120
723
1,26
2240
758
1,46
2360
793
1,68
Units with Vertical Discharg
CAUDAL
Air
50
(l/s)
RPM
BkW
1770
661
0,86
1880
697
1,02
2000
733
1,21
2120
770
1,41
2240
807
1,64
2360
-
-
References
kW - kW input to the motor.
NOTES:
1. In order to change the revolutions it is necessary to change the pulleys and belts on-site.
2. The value includes loss per fi lter, unit cover, and wet coil.
3. Extensive electric and motor tests ensure their use in all operating ranges with maximum reliability.
To use the motor above the recommended values does not imply in an early damage. The unit
warranty will not be affected.
4. The interpolation is allowed. Do not extrapolate.
5. The static pressure loss (economizer, electric heater) must be set at the outside static pressure before
entering at the performance table of the fans.
Fan Performance (SI) - 50TCN120 (50Hz)
PRESSIÓN ESTÁTICA EXTERIOR DISPONIBLE (Pa)
AVAILABLE EXTERNAL STATIC PRESSURE (Pa)
100
150
RPM
BkW
RPM
BkW
679
0,90
734
1,04
709
1,06
761
1,20
741
1,23
790
1,39
773
1,42
820
1,58
805
1,63
-
-
-
-
PRESSIÓN ESTÁTICA EXTERIOR DISPONIBLE (Pa)
AVAILABLE EXTERNAL STATIC PRESSURE (Pa)
100
150
RPM
BkW
RPM
BkW
719
1,01
773
1,15
753
1,18
804
1,33
787
1,37
836
1,54
821
1,59
-
-
-
-
-
-
-
200
RPM
BkW
RPM
786
1,19
837
812
1,36
860
838
1,54
885
866
1,75
-
-
-
-
-
-
-
-
-
200
RPM
BkW
RPM
822
1,29
869
852
1,48
897
883
1,70
-
-
-
-
-
-
-
-
-
-
-
-
-
250
300
BkW
RPM
BkW
1,33
885
1,48
1,51
907
1,67
1,70
-
-
-
-
-
-
-
-
-
-
-
250
300
BkW
RPM
BkW
1,44
912
1,58
1,64
-
-
-
-
-
-
-
-
-
-
-
-
-
-
350
RPM
BkW
932
1,64
-
-
-
-
-
-
-
-
-
-
37