Calculating Settings (SC-SL3NA-BE only)
1 Unit Defi nition
1. Press the UNIT DEFINITION button on the SYSTEM CONFIGURATION screen.
The UNIT DEFINITION screen is displayed.
2
2. Press the item to be set or changed on the list.
Each time the "TYPE" item is pressed, the unit type changes.
MULTI1
: calculating according to the amount of refrigerant fl ow. Used for KX Series and GHP.
MULTI2
: thermo ON/OFF calculating. Used for KX Series and GHP.
RUN/STOP : calculating according to the unit operating time. Used for KX series, PAC and GHP.
If the "CAPACITY" item is pressed, it can be changed. (0 – 200 [kW])
To change the page, press the PREV or NEXT button.
Note
• Please select same item for same system of wattmeter or gas meter.
• When you select MULTI1 or MULTI2, fan mode units are out of calculation. To calculate the fan mode
units, please select RUN/STOP.
• Standby energy used during night etc. is not included in the calculation, and does not equal the value of
wattmeter or gas meter. Please correct the calculation by spreadsheet.
3. Press the SET button. Press the Yes button on the confi rmation screen.
When you do not want to make the setting, press the No button.
If the BACK button is pressed, it returns to the SYSTEM CONFIGURATION screen.
2 Setting the period for calculation
You can divide a day into two period for calculation.
If it is not necessary to devide the period into two parts, you can set the period time for 0:00 - 24:00.
1. Press the ACCOUNTING PERIOD button on the SYSTEM CONFIGURATION screen.
2
2. Press the hour or minute buttons for the start time or the end time.
Input the time.
3. Press the SET button. Press the Yes button on the confi rmation screen.
When you do not want to set, press the No button.
If the BACK button is pressed, it returns to the SYSTEM CONFIGURATION screen.
Caution
The energy consumption calculated by this unit does not conform to OIML, and there are no guar-
antees concerning the results of the calculations.
This unit calculates only energy consumption distribution (gas, electric power). You need to calcu-
late the air-conditioning rates.
The calculating data for twelve months are saved.
See page 28 (Using USB Memory) for the method for extracting calculating data.