Electrical Connections; Wiring Requirements; Electrical Installation - Carel HumiSonic Manual Del Usuario

Humidificadores por ultrasonidos
Ocultar thumbs Ver también para HumiSonic:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

ENG

5.1 Wiring requirements

C
1. Unscrew the screw (A) and remove the cover (B);
2. If the humidifier is wall-mounted/installed on a horizontal support,
remove the corresponding metal knock-out using cutting nippers on
the bottom/rear panel (C);
3. Fit the cable gland (D).

5.2 Electrical installation

WARNING: electric shock hazard. Before making the electrical
connections, the appliance must be disconnected from the mains
power supply and must be prevented from being powered on.
Electrical disconnection must be verified by measurement.
NOTICE:
• check that the unit's power supply voltage corresponds to the rated
data shown on the product label;
• do not power on the unit if tilted or upside down: the transducers may
be damaged.
Connect the power cable to the terminal block through the cable gland.
NOTICE:
to avoid unwanted interference, the power cables should be
kept separate from the probe signal cables.
The humiSonic electronic control board in fact comprises two boards,
a main board (1) installed horizontally, and an auxiliary card (2) installed
vertically.
J8
M9
M15
BOTTOM
Direct version for room applic. +0300062EE - rel. 1.4 - 24.09.2020

5. ELECTRICAL CONNECTIONS

A
B
D
Fig. 5.a
L N
PE
Fig. 5.b
M10
J17
BOARD 2
BOARD 1
M11
M14
Fig. 5.c
MAIN BOARD
C
N
M 15
Key:
A
Board power supply input from transformer 24 V
B
Transducer control
C
Valve power (L drain / R fill)
D
Configuration dipswitches
E
RESERVED
F
Power ON/OFF switch lights
G
TH temperature and humidity probe connection (IIC digital serial, part no.:
HYHU000000) built-in on part numbers UU**R*AS*1.
M14
Remote ON/OFF (M14.1-M14.2)
RS4845 serial (M11)
M11
M15
Front fan power
N
Auxiliary card connection
AUXILIARY CARD
M9
J8
tLan
Tx/Rx GND
J8
tLAN terminal connection (optional)
M9
tLAN auxiliary serial connector
M10
M10.1 - + proportional control signal/probe/humidistat
M10.2 - GND reference signal
M10.3 - +21 Vdc for power to active probes
M10.4 - Alarm relay - CO
M10.5 - Alarm relay - NO
J17
Reserved
Dipswitch configuration: configuration must be performed before
switching on the humidifier (default position shown in Fig. 3.f ).
ON
1
2
1.
Communication
OFF Serial 485 Carel/Modbus
ON
tLAN
2-3 tLAN address (if 1 is ON)
OFF/OFF - -
OFF/ON address 1
ON/OFF address 2
ON/ON address 3
4
Serial 485 / tLAN baud rate
OFF
19200
ON
9600
12
A
B
G
G0
D
E
F
G
M 11
M 14
Fig. 5.d
M10
J17
1
2
3
4
5
NO
COMMON
Fig. 5.e
3
4
5
6
7
8
Fig. 5.f
5-6 Humidity set point
OFF/OFF 50 %rH
OFF/ON
30 %rH
ON/OFF
40 %rH
ON/ON
60 %rH
7
RESERVED
8
Transducer prod. management
OFF parallel
ON series
Tab. 5.a