ENG
"I"
integer variables (Modbus®: REGISTERS)
CAREL
Modbus®
89
216
Secondary humidifier 1 status
92
219
Secondary 1 parameter d3: Operating hour counter
93
220
Secondary 2 firmware release
95
222
Secondary humidifier 2 status
98
225
Secondary 2 parameter d3: Operating hour counter
99
226
Secondary 3 firmware release
101
228
Secondary humidifier 3 status
104
231
Secondary 3 parameter d3: Operating hour counter
105
232
Piezoelectric transducer operating hour counter
106
233
Parameter d6: Time remaining to end of piezoelectric transducer life
107
234
Parameter AF: Piezoelectric transducer working life
112
239
Parameter bH: Enable TH probe as humidity / dew point limit
113
240
Parameter SL: Humidity / dew point limit set point
114
241
Parameter bP: proportional band for control with probe TH or external probe
115
242
Parameter bL: limit proportional band
117
244
Parameter d7: Secondary unit production management
"D"
digital variables (Modbus®: COILS)
CAREL
Modbus®
2
1
Just-started flag
3
2
Humidifier ready to produce
4
3
Set point reached
5
4
Green LED
6
5
Red LED
7
6
Yellow LED
8
7
Remote OnOff
9
8
Low level
10
9
High level
11
10
Aux level
12
11
Autotest completed
14
12
BMS serial in Tlan mode
15
14
TAM enabled
16
15
TAM reading
17
16
Terminal connected
18
17
Production in progress
19
18
Fill
20
19
Drain
21
20
Trasduttore1
22
21
Trasduttore2
23
22
Fan
24
23
Alarm relay
25
24
Auxiliary relay
10.2 Production control via network
To control production via a network connection, configure the humidifier
using following parameters:
digital 27, digital 37 and integer 60 (Modbus 188)
When D37 is set to 1, the humidifier ignores the external control signals
(external controller or probes) and uses the value of integer 60 (Modbus
188) as the control signal. Humidity production can be managed in two
modes:
To manage production as a percentage:
• Set D 37 = 1;
• Set parameter A0 = 1 (Carel 20, Modbus 148, proportional mode);
• Set Carel integer variable 60 (Modbus 188) to the desired level (0-1000
= 0-100.0%).
To manage production with a humidity probe managed by the Main unit:
• Set D 37 = 1;
• Set parameter A0 = 2 (Carel 20, Modbus 148, humidity probe mode);
• Set Carel integer variable 60 (Modbus 188) to the desired level (0-1000
= 0-100.0 rH%);
• Set Carel integer variable 52 (Modbus 180) to the desired humidity set
point.
When D37 is set to 1, if communication is lost for the number of seconds
set by parameter C4, the "Main Offline" alarm is activated (see Alarm table)
and production stops.
Production can be activated/deactivated via digital parameter D27 (see
the Parameter table).
If D27 = 1 the humidifier is disabled and production stops
if D27 = 0 the humidifier is enabled and production is activated.
D27 is independent from the status of D37.
Direct version for room applic. +0300062EE - rel. 1.4 - 24.09.2020
"D"
R/W
CAREL
Modbus®
R
26
25
R
27
26
R
28
27
R
29
28
R
30
29
R
30
31
R
31
30
R
33
31
R
34
33
R
35
34
R
36
35
R
37
36
R
38
37
R
39
38
R
43
42
R
44
43
R
46
45
R
47
46
R
49
48
R
50
49
R
51
50
R
52
51
R
54
53
10.3 Washing cycle activation via network
A washing cycle can be performed at any time by managing digital
variable 38.
Setting the variable to 1 will immediately activate a washing cycle, even
if the unit is in standby, and even if both automatic washing and washing
due to inactivity are disabled by their corresponding parameters.
The variable will keep the value 1 throughout the duration of the washing
cycle, and will automatically be reset at the end of the cycle.
24
digital variables (Modbus®: COILS)
Manual drain
Disable via serial
Reset counter
Resetting the alarms
Washing due to inactivity activated
Status of dipswitch 8: modulation in parallel/series
Functional test completed
Unit of measure
Secondary 1 online
Secondary 2 online
Secondary 3 online
Enable control via serial
Washing activated via serial
Skip autotest or washing while running
Reset piezoelectric transducer hour counter
Backup unit ready to produce
Production limitation in progress (limit probe function)
On/off control via Main/Secondary network
On/off control from Main unit keypad
On/off control from Secondary unit 1 keypad
On/off control from Secondary unit 2 keypad
On/off control from Secondary unit 3 keypad
Parameter bn: disable alarm buzzer
R/W
R
R/W
R
R
R/W
R
R
R/W
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
Tab. 10.f
R/W
R/W
R/W
R/W
R/W
R
R
R
R/W
R
R
R
R/W
R/W
R/W
R
R
R/W
R/W
R/W
R/W
R/W
R/W
Tab. 10.g