Alarms - Carel HumiSonic Manual Del Usuario

Humidificadores por ultrasonidos
Ocultar thumbs Ver también para HumiSonic:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Signal
Code and
Red LED (*)
symbol
on display
(flashing)
2 fast flashes
Et
-
5 fast flashes
EP
3 fast flashes
EF
4 fast flashes
Ed
5 slow flashes
CL
6 fast flashes
PU
-
2 slow flashes
H ¯
3 slow flashes
H_
4 slow flashes
EE
1 fast flash
E0
7 slow flashes
OFL
8 fast flashes
EL
6 slow flashes
ES1
ES2
ES3
1 slow flash
-bu
9 fast flashes
EtL
To reset the alarms, press ESC once to mute the buzzer, press ESC a
second time to completely reset the alarm.
(*) Fast flash: 0.2 seconds ON and 0.2 seconds OFF
Slow flash: 1 second ON and 1 second OFF

11. ALARMS

Meaning
Cause
Autotest failed
- Fill not connected or
insufficient
- drain open
- faulty float
no production
malfunction
of piezoelectric transducers
no water
Interruption to feedwater
supply or fill solenoid valve
malfunction
drain fault
Drain solenoid valve/circuit
malfunction
tank maintenance
Operating hours for
request signal
recommended maintenance
(b5) exceeded
External control
Cable interrupted/
disconnected/
signal not connected
not connected properly.
correctly
High humidity
The signal from the probe
indicates humidity above
80%rH
Low humidity
The signal from the probe
indicates humidity less than
20%rH
EEPROM alarm
Parameter memory
corrupted
Functional test not
Functional test not
performed by manufacturer/
performed
EEPROM problems
Main unit offline
No communication with
the Main unit via serial (if
D37=1)
Water level alarm
Level too high during
atomised water production
due to:
• fill SV leak
• transducer malfunction
• fan malfunction
Alarm on Secondary
Display Secondary unit from
unit 1/2/3
terminal for details of the
alarm
Backup unit not
The backup unit is off or
available
has an alarm: contact J17
on the main unit is open
End of piezoelectric
The unit has reached AF
transducer life
working hours (default
9999 h)
Solution
Check:
• feedwater supply and fill
valve;
• blockage of filter on fill
solenoid valve;
• drain solenoid valve and
drain connection;
Carry out
maintenance on the tank
Check:
• feedwater supply and fill
valve;
• blockage of filter on fill
solenoid valve;
check drain valve and drain
connection
Carry out maintenance on tank
and transducers (chap. 12)
Check the reference signal (4
to 20 mA or 2 to 10V).
Check humidity probe signal/
cable
Check humidity probe signal/
cable
If the problem persists, contact
the CAREL service centre
If the problem persists, contact
the CAREL service centre
Check Main unit status /
communication cable
Check:
• fill SV
• transducers
• fans
see specific alarm
code, chapter "Network
connection"
Check the connection
from the alarm relay on the
backup unit to input J17 on
the main unit.
Replace the piezoelectric
transducers to guarantee
rated unit production
25
Direct version for room applic. +0300062EE - rel. 1.4 - 24.09.2020
Alarm relay
Action
Reset
activation
yes
humidification
ESC / Digital
interrupted
29
yes
humidification
ESC / Digital
interrupted
29
yes
humidification
automatic
(in 10 minute
interrupted only
(after 10
waiting
for 10 minutes
minute wait,
time)
see chap. 8.5)
yes
humidification
ESC / Digital
interrupted
29
no
signal only
Reset hour
counter (see
chap. 6.6 or
7.8)
yes
humidification
AUTO
interrupted
yes
humidification
AUTO
interrupted
yes
humidification
AUTO
interrupted
yes
humidification
If it persists,
contact
interrupted
service
yes
humidification
If it persists,
contact
interrupted
service
yes
humidification
AUTO
interrupted
yes
humidification
AUTO
interrupted
yes
signal only
AUTO
no
signal only
AUTO
yes
signal only
Reset internal
piezoelectric
transducer
counter
by setting
parameter d6
to zero (see
chapter 7.8)
ENG
Tab. 11.a