INSTALLATION
Recommendations:
The device should be installed at least
30 cm from other switching devices.
Avoid installing near equipment liable
to cause electro-magnetic interference
or subjecting the device to vibrations
in excess of 1G with 60Hz frequencies.
SOCOMEC - Ref. : 875 091A
The ATp is installed on the cabinet's
front panel and can mounted using
4 transparent clips.
CLIMATIC ENVIRONMENT
For optimum operation this device
should be used within a temperature
range of -10° C up to 55° C with a
maximum relative humidity of 95%.
SAFETY INSTRUCTIONS
To avoid damage to the device please
ensure the following points are res-
pected before connecting:
• enclosure indications,
• 50 or 60Hz network,
• 230 or 400 V AC voltage +/- 20%
(other voltage requirements on re-
quest),
CONNECTIONS TO THE NETWORK
3 WIRES WITH 3 CT
L1
L2
L3
FUSES
0.5 A
1
N
S1
0 V
1
I1
230 V AC
2
S2
2
400 V AC
3
L1
S1
I2
S2
3
L2
S1
I3
S2
4
L3
4
5
5 4
3 2 1
kWh
3 WIRES WITH 2 CT
L1
L2
L3
FUSES
0,5 A
1
N
1
S1
0 V
I1
230 V AC
2
S2
2
L1
400 V AC
3
S1
I2
S2
3
L2
S1
I3
S2
4
L3
4
5
5 4
3 2 1
kWh
• 760 V AC measuring voltage bet-
ween phases,
• 7 A maximum current (connected
via current transformer(s).
3 WIRES WITH 2 CT
P1
L1
S1
P1
L2
S1
P1
L3
S1
FUSES
0,5 A
1
2
3
4
3 WIRES WITH 1 CT
P1
L1
S1
L2
P1
L3
S1
FUSES
0,5 A
1
2
3
4
P1
S1
P1
S1
N
S1
0 V
1
I1
230 V AC
2
S2
400 V AC
3
L1
S1
I2
S2
L2
S1
I3
S2
L3
4
5
5 4
3 2 1
kWh
P1
S1
N
S1
0 V
1
I1
230 V AC
2
S2
400 V AC
3
L1
S1
I2
S2
L2
S1
I3
S2
L3
4
5
5 4
3 2 1
kWh
13