Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 44

CONFIGURATION

NB:
The device will automatically quit the
configuration menu if no button are
pressed for a period of 25 seconds.
NB:
Press the
button for a prolonged
period to scroll rapidly through the
configuration screens. Press for a
short period to scroll through each
screen one-by-one.
NB:
Press the
button for a prolonged
period to scroll rapidly thorough the
configuration screens. Press for a
short period to scroll incrementally
by 10.
NB:
Press the
button for a prolonged
period for rapid scrolling. Press for a
short period for step by step scrolling.
SOCOMEC - Ref. : 875 091A
KEYS
+
INSTRUCTIONS
Press for 3 seconds to gain
access-code entry.
To enter code 167.
To accept code and access network
configuration (nET).
To select network type
1bL (single phase), 2bL (two-phase),
3-4 nLb (unbalanced three-phase)
and 3-4 bL (balanced three-phase).
To accept network configuration
and pass to CT primary.
To configure primary value up to
6000A.
To accept this configuration value
and pass to voltage transformer (Vt).
To select Vt: 'YES' or 'NO'.
To accept Vt and pass to primary
configuration (VtP).
To configure primary value up to
230.0 kV.
To accept primary configuration
and pass to the same transformer's
secondary (VtS).
To select VtS value (100, 110, 173
or 190V).
15

Publicidad

Tabla de contenido
loading

Tabla de contenido