Installation and Connection
1.2 Control circuit
Version S
1.2.1 Assignment of
Terminal Strip X1
PIN
Function
X1.1
NO contact
X1.2
Opening contact
X1.3
Switching contact
GB
X1.4
Fixed frequency 1
X1.5
Fixed frequency 2
X1.6
Digital Mass
X1.7
+10V
X1.8
Set value input
X1.9
Common
X1.10 Analog output
X1.11 15V
X1.12 Reverse
X1.13 Forward
X1.14 Control release
1.2.2 Connection of the
control
1.2.3 Digital inputs
1.2.4 Analog inputs
28
Name
Description
RLA
Relay output
RLB
Function see parameter CP.22
RLC
( factory setting: fault indication)
I1
X1.4 + X1.5 = fixed frequency 3
I2
no input = analog set value
0V
Potential for digital in-/outputs
CRF
Supply voltage for set value potentiometer (max. 4mA)
REF
0...10VDC for analog set value
COM
Mass for analog in- and outputs
AOUT
Analog output of real frequency 0...10VDC = 0...100Hz
+15V
voltage supply for digital in-/outputs (max. 100mA)
R
Preset rotation; forward has priority
F
ST/RST Power modules are triggered; if opening in case of error
Reset; if opening during operation, the motor costs.
In order to prevent a malfunction caused by interference voltage supply
on the control inputs, the following directions should be observed:
- Use shielded/drilled cables
- Lay shield on one side of the inverter onto earth potential
- Lay control and power cable separately (about 10...20 cm apart)
EMC
- Lay crossings in a right angle (in case it cannot be prevented)
Internal voltage supply
4
5
11 12 13 14
Internal analog set-point
setting 0...10V
7
8
9
R = 3...10 kΩ
1 2 3 4 5 6 7 8 9 10 11 12 13 14
External voltage supply
4
PE
External analog
set-point setting
PE
5
6
12 13 14
+
13...30VDC
8
9
PE
+
-
0...10 DCV
Ri = 4 kΩ
SPS
PE