Using the Store Function
Store/Recall button:
The screen will be flashing the MEM symbol and the number of the
stored data twice when the Store/Recall button is pressed.
1. Press once to store the voltage value during voltage test
2. Press once to store the PI/ DAR, insulation or Earth-bond
resistance value when the individual test is completed.
3. The memory is divided into five segments, each segment has
100 maximum data points. The method to store the data is first
in/first out when the memory is full.
Table: The stored values of the individual test
segments
Earth-Bond
Voltage
resistance
items
1
Voltage
Resistance
2
3
Note: Press the Store/Recall button
The screen will be flashing MEM symbol and "cLr" on reading twice.
Using the Recall Function
>
Press the Store/Recall button
2 sec to enter the RECALL mode.
If the memory is empty, the meter will display the " nOnE " symbol.
Search the stored value under RECALL mode
Insulation
resistance
DAR
PI
50~1000V
Resistance
DAR value
PI value
Leakage
R30-sec
R1-min
Current
Test voltage
R1-min
R10-min
>
5 sec to clear the stored data.
11
Read the stored value of insulation test under RECALL mode
Read the stored value of DAR test under RECALL mode
Press the PI/DAR button > 2 sec to choose the PI/DAR function, and
Press the Store/Recall button > 2 sec to enter the RECALL mode.