3. Installation and Wiring
Non-Tripp Lite External Battery Cabinet Connection
When connecting a non-Tripp Lite external battery cabinet to the UPS, an appropriate 4-pole non-fuse DC breaker and fast-acting fuses
must be installed. Do not use an AC breaker. Locate the breaker and the fuses as close as possible to the batteries. Refer to the figure
below.
• The parallel UPS systems can connect with common batteries.
Note: Parallel UPS systems can connect with common batteries; however, if paralleling UPS systems for redundancy, Tripp Lite does not recommend the
use of a common battery.
WARNING:
A battery can present a risk of electric shock and high short-circuit current. Servicing of batteries and battery
cabinets must be performed or supervised by qualified service personnel knowledgeable in batteries, battery
cabinets and the required precautions. Keep unauthorized personnel away from batteries and battery cabinets.
Battery Status Alarm
When the UPS system's batteries experience one of the problems shown below, the system will sound the following alarms:
No.
External Battery Cabinet Status
1
Battery Test Fail
2
Battery Low Warning
3
Battery Low Shutdown
4
Battery Over Charge
5
Battery Missing
External Battery Cabinet
External Battery Cabinet
External
Battery
Cabinet
+ -
+ -
(Figure 3-15: Non-Tripp Lite External Battery Cabinet Connection)
(N)
+
(
)
External Battery Cabinet
Fast-acting
Fuses
4-pole Non-fuse
DC Breaker
+ -
+ -
+ -
Alarm
Sounds once every 2 seconds
Sounds once every 0.5 second
Long beep (5 seconds)
Sounds once every 2 seconds
Sounds once every 2 seconds
17
-
(
)
+ -