We would like to thank you for having purchased our cassette type fan coil "FCA" Aermec.
It is made with high quality material, in strict compliance to "FCA" safety norms and is easy to use and is long lasting.
DESCRIPTION OF THE UNIT
PURPOSE OF THE MACHINE
The cassette type fancoil unit is a terminal for the treatment of
air in a room regardless of whether it is summer or winter.
The unit is ceiling-mounted with the possibility of treating fresh
outside air and sending treated air to an adjacent rooms.
CHARACTERISTICS
- Ventilating axial-centrifuge 4-speed unit.
- Very quiet operation.
- Great well-designed grille appearance.
- Grille dimensions respect standard suspending ceiling
panel sizes (600x600 mm), with single-panel units (single)
and higher power for two panels (twin).
- Continuous fan functioning to avoid the air becoming stra-
tified.
- Possibility of outside air being brought in.
It is also possible to cool one or two adjacent rooms.
- Easy to install and maintain.
- Electrostatically pre-charged, self-bearing filter, featuring
great efficiency and low pressure drops Fire Resistance
Class 2 (UL900).
- Air filter easy to remove and clean with vacuum cleaner.
- Standard hot/cold battery valve. .
- Full compliance with accident protection regulations.
OPERATION
FCA: usage instructions are contained in the manuals supplied
with the command panels.
PACKAGING
The cassette fan coils are sent in standard packaging made of
foam polystyrene and cardboard.
OPERATIONAL LIMITS
Maximum water input temperature
Maximum operating temperature
Maximum height off the ground
The assembly site must be chosen in such a way that the
maximum and minimum ambient temperature limits Ta are
respected 0°C < Ta < 45°C ; R.H. < 85%.
The FCA cassette fan coils are powered with a voltage of 230
V monophase at 50 Hz and ground connection, in any case
the power of the line must remain within the limit of ±10%
with respect to the nominal value.
If the fan coil is working in cold continuous mode inside an
environment where the relative humidity is high, condensa-
te might form on the air delivery. Said condensate might be
deposited on the floor and on any objects underneath. To
MINIMUM AVERAGE WATER TEMPERATURE
Wet bulb temperature °C
10
AVAILABLE VERSIONS AND SIZES
The FCA and FCA-R fancoil units are available in:
5 sizes for two-pipe systems
5 sizes for four-pipe systems
FCA-R: usage instructions are contained in the manual FCA-R
directions for use.
80 [°C]
8 [bar]
3 [m]
avoid condensate on the external structure of the apparatus
with the fan in operation, the average temperature of the
water must not be lower than the limits shown in the table
below, that depend on the thermo-hygrometric condition of
the air in the environment. The above limits refer to fan move-
ment at minimum speed.
The use of water at high temperatures could cause squeaking
due to the different thermal expansions of the elements (pla-
stics and metals), this does not however cause damage to the
unit if the maximum operating temperature is not exceeded.
21
23
15
3
3
17
3
3
19
3
3
21
6
5
23
-
8
FCA 32
FCA 32 R1
FCA 36
FCA 36 R1
FCA 42
FCA 42 R1
FCA 62
FCA 62 R1
FCA 82
FCA 82 R1
FCA 122
FCA 122 R1
FCA 34
FCA 34 R1
FCA 38
FCA 38 R1
FCA 44
FCA 44 R1
FCA 64
FCA 64 R1
FCA 84
FCA 84 R1
FCA 124
FCA 124 R1
Dry bulb temperature °C
25
27
3
3
3
3
3
3
4
3
7
6
Mono
Mono
Mono
Mono
Twin
Twin
Mono
Mono
Mono
Mono
Twin
Twin
29
31
3
3
3
3
3
3
3
3
5
5