8 Diagnosis, asset management and service
Code
Cause
Text mes-
sage
•
F013
Sensor does not
detect an echo
no measured
during operation
value availa-
•
Antenna system
ble
dirty or defective
•
F017
Adjustment not
within specifi-
Adjustment
cation
span too
small
•
F025
Index markers
are not conti-
Error in the li-
nuously rising,
nearization
for example
table
illogical value
pairs
•
F040
Hardware defect
Error in the
electronics
•
F080
General soft-
ware error
•
F105
The instrument
is still in the
Determine
start phase, the
measured
measured value
value
could not yet be
determined
•
F113
EMC interfe-
rence
Communica-
tion error
•
F125
Temperature of
the electronics
Impermissib-
in the non-
le electronics
specified range
temperature
•
F260
Error in the
calibration
Error in the
carried out in the
calibration
factory
•
Error in the
EEPROM
32
Rectification
•
Check or correct
installation and/
or parameter
settings
•
Clean or
exchange pro-
cess component
or antenna
•
Change adjust-
ment according
to the limit
values (diffe-
rence between
min. and max.
≥ 10 mm)
•
Check linearisa-
tion table
•
Delete table/
Create new
•
Exchanging the
electronics
•
Function check
Send instrument
for repair
The following table shows the error codes and
•
text messages in the status message "Function
Disconnect ope-
check" and provides information on causes as
rating voltage
well as corrective measures.
briefly
•
Wait for the end
of the switch-on
phase
•
Duration up to
approx. 3 minu-
tes depending
on the version
and parameter
settings
•
Remove EMC
Out of specification
influences
The following table shows the error codes and
text messages in the status message "Out of
•
specification" and provides information on cau-
Check ambient
ses as well as corrective measures.
temperature
•
Exchanging the
electronics
•
Send instrument
for repair
Code
Cause
Text mes-
sage
•
F261
Error during
setup
Error in the
•
False signal
configuration
suppression
faulty
•
Error when
carrying out a
reset
•
F264
Adjustment not
within the vessel
Installation/
height/measu-
Setup error
ring range
•
Max. measuring
range of the
instrument not
sufficient
•
F265
Sensor no lon-
ger carries out a
Measure-
measurement
ment function
•
Operating vol-
disturbed
tage too low
Code
Cause
Text mes-
sage
•
C700
A simulation is
active
Simulation
active
Code
Cause
Text mes-
sage
•
S600
Temperature of
the electronics
Impermissib-
in the non-
le electronics
specified range
temperature
VEGAPULS WL S 61 • 4 ... 20 mA
Rectification
•
Repeat setup
•
Repeat reset
•
Check or correct
installation and/
or parameter
settings
•
Use an instru-
ment with bigger
measuring
range
•
Check operating
voltage
•
Carry out a reset
•
Disconnect ope-
rating voltage
briefly
Rectification
•
Finish simulation
•
Wait for the
automatic end
after 60 mins.
Rectification
•
Check ambient
temperature