8 Diagnosis, asset management and service
Code
Cause
Text mes-
sage
F013
Sensor does not
detect an echo
no measured
during operation
value availa-
Antenna system
ble
dirty or defective
F017
Adjustment not
within specifi-
Adjustment
cation
span too
small
F025
Index markers
are not conti-
Error in the li-
nuously rising,
nearization
for example
table
illogical value
pairs
F040
Hardware defect
Error in the
electronics
F080
General soft-
ware error
F105
The instrument
is still in the
Determine
start phase, the
measured
measured value
value
could not yet be
determined
F113
EMC interfe-
rence
Communica-
tion error
F125
Temperature of
the electronics
Impermissib-
in the non-
le electronics
specified range
temperature
F260
Error in the
calibration
Error in the
carried out in the
calibration
factory
Error in the
EEPROM
32
Rectification
Check or correct
installation and/
or parameter
settings
Clean or
exchange pro-
cess component
or antenna
Change adjust-
ment according
to the limit
values (diffe-
rence between
min. and max.
≥ 10 mm)
Check linearisa-
tion table
Delete table/
Create new
Exchanging the
electronics
Function check
Send instrument
for repair
The following table shows the error codes and
text messages in the status message "Function
Disconnect ope-
check" and provides information on causes as
rating voltage
well as corrective measures.
briefly
Wait for the end
of the switch-on
phase
Duration up to
approx. 3 minu-
tes depending
on the version
and parameter
settings
Remove EMC
Out of specification
influences
The following table shows the error codes and
text messages in the status message "Out of
specification" and provides information on cau-
Check ambient
ses as well as corrective measures.
temperature
Exchanging the
electronics
Send instrument
for repair
Code
Cause
Text mes-
sage
F261
Error during
setup
Error in the
False signal
configuration
suppression
faulty
Error when
carrying out a
reset
F264
Adjustment not
within the vessel
Installation/
height/measu-
Setup error
ring range
Max. measuring
range of the
instrument not
sufficient
F265
Sensor no lon-
ger carries out a
Measure-
measurement
ment function
Operating vol-
disturbed
tage too low
Code
Cause
Text mes-
sage
C700
A simulation is
active
Simulation
active
Code
Cause
Text mes-
sage
S600
Temperature of
the electronics
Impermissib-
in the non-
le electronics
specified range
temperature
VEGAPULS WL S 61 • 4 ... 20 mA
Rectification
Repeat setup
Repeat reset
Check or correct
installation and/
or parameter
settings
Use an instru-
ment with bigger
measuring
range
Check operating
voltage
Carry out a reset
Disconnect ope-
rating voltage
briefly
Rectification
Finish simulation
Wait for the
automatic end
after 60 mins.
Rectification
Check ambient
temperature

Publicidad