HC151 PHRX
Digital multifunction solenoid metering pump
4.1.5 SETUP – INHIBIT
The INHIBIT menu allows you to set the inhibit function.
You can't set inhibit input for 6-7-8 pump models.
The menu consists:
4.1.6 SETUP – RELAY OUTPUT
RELAY OUTPUT menu allows you to set the relay's working mode.
ENTER
Dosing rep
ADSP9500092
NO
ENTER
YES
Press and hold the ESC key to return to the previous menu.
SETTING RELAY
ENTER
MODE
DOSING REP./ALARM
ENTER
ENTER
RELAY
OPEN DOSAGE/
CLOSE DOSAGE
Press and hold the ESC key to return to the previous menu.
14/04/2015 Rev. 1.0
INHIBIT
ENTER
Use the Up and Down keys to enable
ENABLE ?
or disable the function.
YES/NO
ENTER
Use the Up and Down keys to set
CONTACT
contact: NO (normally open) or NC
NO/NC
(normally close)
Use the UpandDown keys to select mode:
DOSINGREP. orALARM
Alarm
If in ALARM mode, the alarm is
signaled on open/close relay
RELAY
In case of DOSING REP. mode, during
OPEN ALARM/
.
dosing relay is open/close.
CLOSE ALARM
Use the Up and Down keys to set.
ENGLISH
41/123