Pressing "R" with empty system, the display will show the message "Empty Circuit!". Press "C/E" to exit.
Country CLIMA is equipped with the MULTIPASS system that optimizes the recovery phase during winter period. (
chapter "Multipass").
Vacuum and Vacuum test function:
Move with arrows on the "V" icon
Press "Enter" to visualize the set vacuum time.
Set with the arrows key the needed vacuum time (recommended min time: 20 min)
To confirm the vacuum time and to start the vacuum phase, press the ENTER key.
If you want to confirm the vacuum time without starting the vacuum phase press the "C/E" key
Following the same procedure also the leak test is available.
If it is set a vacuum time > 0, the vacuum test is performed automatically. At the end of the programmed time, if no
leaks are found into the A/C system, on the display the message "Print Report" is displayed (printer version only)
If there is a leak, the message "System Leaks!" will appear.
(only if previously programmed vacuum test);
In this case use special kit (leak detector lamp) (optional) to localize the leaks.
Press "C/E" to exit.
Note: In order to make the vacuum phase it is necessary that the AC system pressure is zero.
If during the vacuum phase, the Station detects a leak, some warning beep will warn the operator.
Oil charge function:
14/04/2016
Print Report ?
System leaks!