3. SYSTEM SUPPLY

To start up the system proceed as follows:
1. Set the Power Supply switch to the ON position and the display will show, in this order:
COMPANY NAME
MODULE LINE Nº
TIME
MODEL
OFF
2. Connect the battery/ies by means of the two pair of cable provided, bearing in mind the polarity (red-
positive, black-negative).

4. CHANGE OF LANGUAGE

If you need to change the language of the displayed messages, proceed as follows with the module line in OFF position.
1. Press FORWARD.
Default language is displayed.
2. Press FORWARD to change it.
3. Press PROGRAMMING to memorise the selected language.

5. CO DETECTION. SPANISH STANDARD. Default configuration

If you have requested EUROSONDELCO for the Carbon Monoxide (CO) detection meeting the Spanish Standard regarding
this gas detection, then your Control Unit will be programmed with the following parameters -default-:
Ventilation -Actuation-
Alarm:
Number of Groups:
Cyclical Ventilation:
Activation time of cyclical ventilation:
System checking interval:
Engineer Code:
If you do not need to change any of the parameters described, it will not be necessary to enter in SYSTEM PROGRAMMING
menu, being able to enter in SYSTEM CONNECTION directly (page nº 54). If you need to change any of the parameters,
go directly to that parameter by pressing FORWARD (see quick programming for this standard in page nº 39).
To change any parameter:
1. Press PROGRAMMING
"Insert Code" will be displayed (engineer). Default setting: 66666 by pressing ENTER 5 times.
2. Press FORWARD to display, in order of appearance, the programmable parameters described next.
Instructions in point QUICK PROGRAMMING can also be taken as reference (page nº 39).
32
32
© 2012 DURAN ELECTRONICA S.L.
All rights reserved · www.duranelectronica.com
ON: 50 ppm -1 min input retard-
OF: < 50ppm -2 min output retard-
ON 100ppm -instant-
1
Each "0" hours
5 min
Each "0" months -without programmed checking-
66666 -5 times ENTER-