9. CO DETECTION, SWISS / GERMAN STANDARD. Default configuration
If you do not need to change any of the parameters described, it will not be necessary to enter the SYSTEM PROGRAMMING
menu.
If you need to change any of the parameters, go directly to that parameter by pressing FORWARD.
4 OPTIONS
2 VENTILATION LEVELS
Ventilation:
Ventilation:
Alarm:
Number of groups:
Cyclical ventilation:
Cyclical ventilation activation time:
Overhauls Interval:
Engineer code:
Ventilation mode:
1 VENTILATION LEVEL
Ventilation:
Alarm:
AVERAGE: 1 VENTILATION EVERY HALF HOUR
Ventilation:
Alarm:
AVERAGE: 2 VENTILATIONS EVERY HALF HOUR
Ventilation:
Ventilation:
Alarm:
1st Speed
ON: 90 ppm -1 minute input retard-
OFF: 80 ppm -1 minute output retard-
2nd Speed
ON: 100 ppm -1 minute input retard-
OFF: 90 ppm -1 minute output retard-
ON 200 ppm -3 minutes input retard-
1
Each "0" hours
5 minutes
Each "0" months
66666 -5 times ENTER -
Instant with 2 relays
ON: 100 ppm -1 minute input retard-
OFF: 80 ppm -1 minute output retard-
ON 200 ppm -3 minute input retard-
ON: 100 ppm -instant when reaching average-
OFF: 80 ppm -instant when reaching average-
ON 250 ppm -instant-
1st Speed.
ON: 90 ppm -instant when reaching average-
OFF: 80 ppm -instant when reaching average-
2nd Speed.
ON: 100 ppm -instant when reaching average-
OFF: 90 ppm -instant when reaching average-
ON 250 ppm -instant-
49
X-maneuro-INS-v04