Wiring Diagram; Wiring Connections - Ashland ANC200 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

WIRING CONNECTIONS

1. All electrical wiring must be in accordance with local
code and only qualified electricians should make the
installations.
2. Three phase pumps - instructions for wiring to control
panel will be included with control panel.
208/230 VOLT - SINGLE PHASE
CONTROL CORD
CONNECTORS
GROUND SCREW
HEAT SENSOR
ELECTRODE
ON STATOR
PROBE TEST RESISTOR ON
HAZARDOUS LOCATION ONLY
Figure 3
Solids Handling Pumps
Models: ANC200/300/500/750/1000/1500 /2000
& ANCV200/300/500/750/1000/1500 /2000

Wiring Diagram

208/230 VOLT - THREE PHASE
POWER CORD
CONTROL CORD
CONNECTORS
HEAT SENSOR
ON STATOR
STATOR
PROBE TEST RESISTOR ON
HAZARDOUS LOCATION ONLY
3. All wires should be checked for shorts to ground with
an ohmmeter or megger after the connections are
made. This is IMPORTANT, as one grounded wire can
cause failure of the pump, control panel or personal
injury.
POWER CORD
GROUND SCREW
ELECTRODE
STATOR
14
460 VOLT - THREE PHASE
CONTROL CORD
CONNECTORS
GROUND SCREW
HEAT SENSOR
ELECTRODE
ON STATOR
PROBE TEST RESISTOR ON
HAZARDOUS LOCATION ONLY
POWER CORD
STATOR

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido