must be equipped with a magnetic cleansing filter with a
filtration capacity of no less than 500 microns and a magnetic
field of no less than 10,000 Gauss (e.g. IDRAMAG F). This
should be installed on the circuit and sized according to
the capacity of the circulation pump.
For installations on new systems, as an alternative to the
system mentioned above, you can also install magnetic
cleansing filters with a magnetic capacity of no less than
1,000 Gauss (e.g. IDRAMAG or IDRAMAG FS). These
should be installed on a branch with a draining capacity of
approximately 10% of the system's total flow rate.
GB
In both cases, you must ensure that the fluid has been
treated with suitable protective agents, as set out in
standard UNI 8065.
Any damage caused by solid, fibrous or abrasive substances
that cannot be attributed to a defect in the original product,
will INVALIDATE THE WARRANTY.

5.2 NOT INTENDED USE

All uses not specifically mentioned in 5.1 are generally
banned; in particular, the fluid must not contain aggressive
or explosive additives, mixtures of mineral oils and/or solid
or fibrous particles. The pump should not be used for
pumping flammable or explosive media, or in an explosive
atmosphere. To avoid formation of condensation in the
pump, fluid temperature must be higher or equal to the
ambient temperature.
6. TECHNICAL AND BUILDING FEATURES
6.1 TECHNICAL DATA
Pump type
Power P
[W]
1
Rated current I
[A]
n
Power Supply
Motor protection
Protection class
Insulation class
Relative humidity
Ambient temperature
Medium temperature
System pressure

6.2 LIMITS OF USE

The minimum pressure at suction shall be:
- 0.05 bar for medium at 50°C
- 0.80 bar for medium at 80°C
- 1.40 bar for medium at 110°C
8
40-80 40-120 40-180 50-80 50-120 50-180 65-80 65-120 65-180 80-80 80-120 80-180
270
480
680
370
1,2
2,3
2,9
1,7
Ego (T) (C) slim
560
800
560
2,5
3,7
2,5
1~230V – 50/60Hz
External protection is not necessary
IP44
F
Max 95%
0-40°C
min -10° max 110° C
Up to 1 MPa (10 bar)
Ambient and medium temperature:
Ambient
Temperature [°C]
Up to 25°C
30°C
35°C
40°C
Working outside of recommended conditions
can shorten life time and nullify the warranty
800
800
3,7
3,7
Medium Temperature
min. [°C]
max. [°C]
-10
-10
-10
-10
110
100
90
80

Publicidad